Emergency telegram
By means of the emergency telegram, the I/O system IP20 communicates internal
device errors to other system bus nodes with high priority. 8 bytes of user data are
available.
Index
Name
Possible settings
Important
Lenze
Selection
I1014
h
COB ID emergency
Emergency telegram
Identifier 80h + node address is displayed
after boot−up.
^ 8.10−2
Emergency telegram structure
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
LOW byte
HIGH byte
Error register
Error information
Error code
Error code
I1001
h
1
2
3
4
5
Contents of the emergency telegram
Error cause
Byte 0
Byte 1
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Emergency telegram reset
0000
h
00
h
00
h
00
h
00
h
00
h
Error on initialisation of modules linked to
backplane bus
1000
h
01
h
00
h
00
h
00
h
00
h
Error on module configuration check
02
h
Slot number
00
h
00
h
00
h
Error on module read/write
03
h
Slot number
00
h
00
h
00
h
Module configuration was changed
05
h
00
h
00
h
00
h
00
h
Configuration of the modules has been
changed. The module is in the Pre−Operational
state.
06
h
00
h
00
h
00
h
00
h
Incorrect module parameterisation
30
h
Slot number
00
h
00
h
00
h
Diagnostic alarm − analog module
40
h
+
Slot number
Diagnostic byte 0 Diagnostic byte 1 Diagnostic byte 2 Diagnostic byte 3
Process alarm − analog module
80
h
+
Slot number
Diagnostic byte 0 Diagnostic byte 1 Diagnostic byte 2 Diagnostic byte 3
PDO control (monitoring time in I2400
h
has
been exceeded).
FF
h
10
h
PDO number
Monitoring time
(LOW byte)
Monitoring time
(HIGH byte)
SDO/PDO mapping error
6300
h
Map index
(LOW byte)
Map index
(HIGH byte)
Number of entries
00
h
00
h
Heartbeat error (monitoring time exceeded).
8130
h
Subindex
Node address
Monitoring time
(LOW byte)
Monitoring time
(HIGH byte)
00
h
Node guarding error (monitoring time
exceeded).
8130
h
Guard time
(LOW byte)
Guard time
(HIGH byte)
Life time
00
h
00