13 parameter setting via profibus−dp – Lenze EPM−T9XX Modular system User Manual
Page 433

Parameterising analog modules
Signal functions of 4xanalog input /output
Parameter setting via PROFIBUS−DP
13.1
13.1.10
L
13.1−21
EDSPM−TXXX−9.0−11/2009
Paramete
r bytes
4/5
Signal function
Signal range
Format
1)
Tolerance
2)
00
h
Parameter data in module are not overwritten
01
h
Voltage signal
output
±10 V
−10.00
−16384
{0.01V}
{1
dec
}
+10.00
+16384
S5
Two’s
complement
±0.2 %
Min.
Limit
values
Max.
−12.50 V
−20480
dec
+12.50 V
+20480
dec
02
h
Voltage signal
output
1 ... 5 V
+1.00
0
{0.01V}
{1
dec
}
+5.00
+16384
S5
Two’s
complement
±0.6 %
Min.
Limit
values
Max.
0.00
−4096
dec
+6.00 V
+20480
dec
05
h
Voltage signal
output
0 ... 10 V
0.00
0
{0.01V}
{1
dec
}
+10.00
+16384
S5
Two’s
complement
±0.4 %
Min.
Limit
values
Max.
0.00
0
+12.50 V
+20480
dec
09
h
Voltage signal
output
±10 V
−10.00
−27648
{0.01V}
{1
dec
}
+10.00
+27648
S7
Two’s
complement
±0.2 %
Min.
Limit
values
Max.
−11.76 V
−32512
dec
+11.76 V
+32511
dec
0A
h
Voltage signal
output
1 ... 5 V
+1.00
0
{0.01V}
{1
dec
}
+5.00
+27648
S7
Two’s
complement
±0.6 %
Min.
Limit
values
Max.
0.00
−6912
dec
+5.704 V
+32511
dec
0D
h
Voltage signal
output
0 ... 10 V
0.00
0
{0.01V}
{1
dec
}
+10.00
+27648
S7
Two’s
complement
±0.4 %
Min.
Limit
values
Max.
0.00
0
+11.76 V
+32511
dec
03
h
Current signal
output
±20 mA
−20.00
−16384
{0.01 mA}
{1
dec
}
+20.00
+16384
S5
Two’s
complement
±0.3 %
Min.
Limit
values
Max.
−25.00 mA
−20480
dec
+25.00 mA
+20480
dec
04
h
Current signal
output
4 ... 20
mA
+4.00
0
{0.01 mA}
{1
dec
}
+20.00
+16384
S5
Two’s
complement
±0.8 %
Min.
Limit
values
Max.
+0.00
−4096
dec
+24.00 mA
+20480
dec
Output functions