4 signal functions of 4xanalog input, Signal functions of 4xanalog input, 13 parameter setting via profibus−dp – Lenze EPM−T9XX Modular system User Manual
Page 419
Parameterising analog modules
Signal functions of 4xanalog input
Parameter setting via PROFIBUS−DP
13.1
13.1.4
L
13.1−7
EDSPM−TXXX−9.0−11/2009
13.1.4
Signal functions of 4xanalog input
)
Note!
l
Short−circuit unused inputs (connect positive and negative
terminals) or deactivate them by assigning the function number
FF
h
.
l
In the event of an overflow or underflow, wrong values are
output. Strong signal jumps with sign reversal may occur.
I/O system IP20 multiplies measured values with decimal positions and without
normalisation by a factor and transfers them as integers to the bus. To output the
decimal positions, divide the measured values by the same factor.
Example:
Measuring task: Temperature measurement with signal function 01
h
. Measured value = 80.5 °C.
1. I/O system IP20 converts the measured value into an integer:
80.5 [°C] × 10 = 805
2. Reconvert the measured value to output it with decimal positions:
805 [°C]
10
+ 80.5 °C
Paramete
r bytes
2/3/4/5
Signal function
Signal range
Format
1)
Tolerance
2)
00
h
18
Parameter data in module are not overwritten
01
h
Temperature
measurement with
two−wire
connection
PT100
−200.0
{0.1 °C}
+850.0
S7
Two’s
complement
±1 °C
3)
02
h
PT1000
−200.0
{0.1 °C}
+500.0
03
h
NI100
−50.0
{0.1 °C}
+250.0
04
h
NI1000
−50.0
{0.1 °C}
+250.0
05
h
Resistance
measurement with
two−wire
connection
60
W
0.00
0
{0.01
W}
{1
dec
}
+60.00
32767
S7
±0.2 % of the
final value
3)
06
h
600
W
0.00
0
{0.01
W}
{1
dec
}
+600.00
32767
07
h
3000
W
0.00
0
{0.01
W}
{1
dec
}
+3000.00
32767
08
h
6000
W
0.00
0
{0.01
W}
{1
dec
}
+6000.00
32767
09
h
Temperature
measurement with
four−wire
connection
PT100
−200.0
{0.1 °C}
+850.0
S7
Two’s
complement
±0.5 °C
0A
h
PT1000
−200.0
{0.1 °C}
+500.0
0Bh
NI100
−50.0
{0.1 °C}
+250.0
0C
h
NI1000
−50.0
{0.1 °C}
+250.0
0D
h
Resistance
measurement with
two−wire
connection
60
W
0.00
{0.01
W}
+60.00
S7
±0.1 % of the
final value
0E
h
600
W
0.00
{0.01
W}
+600.00
±0.05 % of
the final value
0F
h
3000
W
0.00
{0.01
W}
+3000.00
±0.05 % of
the final value
10
h
Temperature
measurement with
thermoelement and
external
compensation
4)
Type J
−210.0
{0.1 °C}
+850.0
S7
Two’s
complement
±1 °C
11
h
Type K
−270.0
{0.1 °C}
+1200.0
±1.5 °C
12
h
Type N
−200.0
{0.1 °C}
+1300.0
±1.5 °C
13
h
Type R
−50.0
{0.1 °C}
+1760.0
±4 °C
14
h
Type T
−270.0
{0.1 °C}
+400.0
±1.5 °C
15
h
Type S
−50.0
{0.1 °C}
+1760.0
±5 °C