Page 472
Parameterising 2/4xcounter module
2 x 32 bit counter with G/RES (mode 27)
Parameter setting via PROFIBUS−DP
13.2
13.2.14
L
13.2−38
EDSPM−TXXX−9.0−11/2009
13.2.14
2 x 32 bit counter with G/RES (mode 27)
epm−t142
Fig. 13.2−49
Terminal assignment of the 2/4xcounter in the mode 27
The mode 27 offers two 32−bit counters which can be assigned with a starting
value.
The counting direction is determined via the signal level at input IN3 / IN6 (DIR):
Upcounter: LOW level
Downcounter: HIGH level
If a HIGH level is applied to input IN3 / IN6 (G/RES), the counter is incremented or
decremented by 1 with each LOW/HIGH edge.
During the counting process a HIGH level must be applied to input IN1 / IN4
(G/RES). With a LOW level the counter content is frozen. With a rising edge at the
input IN1 / IN4 (G/RES) the counter is deleted.
When the counter reaches zero, the output OUT0 / OUT1 is set to HIGH level for
at least 100 ms, even if the counter continues to count. When the counter stops
at zero, the output OUT0 / OUT1 remains on the HIGH level.
Terminal assignment
DIR signal
CLK signal
G/RES signal
OUT signal