6 example of parameter setting via process data, Example of parameter setting via process data – Lenze EPM−T9XX Modular system User Manual
Page 390

Parameterising SSI interface
Example of parameter setting via process data
Parameter setting via system bus (CAN) / CANopen
12.5
12.5.6
L
12.5−14
EDSPM−TXXX−9.0−11/2009
12.5.6
Example of parameter setting via process data
The station consists of a CAN gateway and an SSI interface. An encoder with a
24−bit resolution and Gray code is used.
Output I/O.0 is to switch with a counter value of > 1000, output I/O.1 with a counter
value of > 2000. For a simpler representation, the figures are provided in a
hexadecimal format.
Selection
Mapping
SSI mapping PLC (I4104
h
= 0)
Node address
2
Coding (I3001/1)
Gray code
Hold function (I3001/1)
Deactivated
1. Assigning parameter data
epm−t188
Fig. 12.5−17
Example − How to assign parameter data when using SSI interface
2. Assigning comparison value for channel 0
epm−t189
Fig. 12.5−18
Example − How to assign a comparison value to channel 0 when using SSI interface
3. Assigning comparison value for channel 1
epm−t190
Fig. 12.5−19
Example − How to assign a comparison value to channel 1 when using SSI interface
Example