10 signal functions 4xanalog output 0 ma, Signal functions 4xanalog output 0 ma – Lenze EPM−T9XX Modular system User Manual
Page 315

Parameterising analog modules
Signal functions 4xanalog output 0...20mA
Parameter setting via system bus (CAN) / CANopen
12.3
12.3.10
L
12.3−17
EDSPM−TXXX−9.0−11/2009
12.3.10
Signal functions 4xanalog output 0...20mA
)
Note!
In the event of an overflow or underflow, wrong values are output.
Strong signal jumps with sign reversal may occur.
Paramete
r bytes
2/3/4/5
Signal function
Signal range
Format
1)
Tolerance
00
h
15
No signal emitted at output
01
h
06
h
Current signal
output
0 ... 20
mA
0.00
0
{0.01 mA}
{1
dec
}
+20.00
16384
S5
Two’s
complement
±0.2 %
2)
±0.4 %
3)
Min.
Limit
values
Max.
0.00
0
+25.00 mA
+20480
dec
04
h
Current signal
output
4 ... 20
mA
4.00
0
{0.01 mA}
{1
dec
}
20.00
16384
S5
Two’s
complement
±0.3 %
2)
±0.5 %
3)
Min.
Limit
values
Max.
0.00
−4096
dec
+24.00 mA
+20480
dec
0C
h
Current signal
output
4 ... 20
mA
4.00
0
{0.01 mA}
{1
dec
}
20.00
27648
S7
Two’s
complement
±0.3 %
2)
±0.5 %
3)
Min.
Limit
values
Max.
0.00
−6912
dec
+22.81 mA
+32511
dec
0E
h
Current signal
output
0 ... 20
mA
0.00
0
{0.01 mA}
{1
dec
}
20.00
27648
S7
Two’s
complement
±0.2 %
2)
±0.4 %
3)
Min.
Limit
values
Max.
0.00
0
+23.52 mA
+32511
dec
FF
h
Analog output is switched off
1)
Format of the output data (
¶ 12.3−7).
2)
Tolerance of the output range at an ambient temperature of 25 °C.
3)
Tolerance of the output range across the entire admissible temperature range.
Lenze setting of the signal function in parameter bytes 2 and 3 or 4 and 5: 06
h