9 signal functions of 4xanalog output ±10, Signal functions of 4xanalog output ±10 – Lenze EPM−T9XX Modular system User Manual
Page 314

Parameterising analog modules
Signal functions of 4xanalog output ±10
Parameter setting via system bus (CAN) / CANopen
12.3
12.3.9
L
12.3−16
EDSPM−TXXX−9.0−11/2009
12.3.9
Signal functions of 4xanalog output ±10
)
Note!
In the event of an overflow or underflow, wrong values are output.
Strong signal jumps with sign reversal may occur.
Paramete
r bytes
2/3/4/5
Signal function
Signal range
Format
1)
Tolerance
00
h
14
No signal emitted at output
01
h
Voltage signal
output
±10 V
−10.00
−16384
{0.01V}
{1
dec
}
+10.00
16384
S5
Two’s
complement
±0.1 %
2)
±0.2 %
3)
Min.
Limit
values
Max.
−12.50 V
−20480
dec
+12.50 V
20480
dec
05
h
Voltage signal
output
0 ... +10
V
0.0
0
{0.1V}
{1
dec
}
+10.0
16384
S5
Two’s
complement
±0.2 %
2)
±0.4 %
3)
Min.
Limit
values
Max.
0.0
0
+12.5 V
20480
dec
09
h
Voltage signal
output
±10 V
−10.00
−27648
{0.01V}
{1
dec
}
+10.00 V
27648
dec
S7
Two’s
complement
±0.1 %
2)
±0.2 %
3)
Min.
Limit
values
Max.
−11.76 V
−32512
dec
+11.76 V
32511
dec
0D
h
Voltage signal
output
0 ... +10
V
0.0
0
{0.1V}
{1
dec
}
+10.0
27648
S7
Two’s
complement
±0.2 %
2)
±0.4 %
3)
Min.
Limit
values
Max.
0.0
0
+11.76 V
32511
dec
FF
h
Analog output is switched off
1)
Format of the output data (
¶ 12.3−7).
2)
Tolerance of the output range at an ambient temperature of 25 °C.
3)
Tolerance of the output range across the entire admissible temperature range.
Lenze setting of the signal function in parameter bytes 2 and 3 or 4 and 5: 01
h