8 signal functions of 4xanalog output, Signal functions of 4xanalog output – Lenze EPM−T9XX Modular system User Manual
Page 311

Parameterising analog modules
Signal functions of 4xanalog output
Parameter setting via system bus (CAN) / CANopen
12.3
12.3.8
L
12.3−13
EDSPM−TXXX−9.0−11/2009
Paramete
r bytes
2/3/4/5
Tolerance
Format
1)
Signal range
Signal function
39
h
Current
measurement
4 ... 20
mA
4.00
0
{0.01 mA}
{1
dec
}
20.00
16384
S5
Two’s
complement
±0.2 %
2)
±0.5 %
3)
Min.
Limit
values
Max.
0.8 mA
−3277
dec
+24.00 mA
+20480
dec
3A
h
3Bh
Current
measurement
±20 mA
−20.00
−16384
{0.01 mA}
{1
dec
}
+20.00
16384
S5
Two’s
complement
±0.1 %
2)
±0.2 %
3)
Min.
Limit
values
Max.
−25.00 mA
−20480
dec
+25.00 mA
+20480
dec
FF
h
Analog input deactivated
1)
Format of the input data (
¶ 12.3−7).
2)
Tolerance of the input range at an ambient temperature of 25 °C.
3)
Tolerance of the input range across the entire admissible temperature range.
Lenze setting of the signal function in parameter bytes 2 and 3 or 4 and 5: 3A
h
12.3.8
Signal functions of 4xanalog output
)
Note!
In the event of an overflow or underflow, wrong values are output.
Strong signal jumps with sign reversal may occur.
Paramete
r bytes
2/3/4/5
Signal function
Signal range
Format
1)
Tolerance
00
h
13
No signal emitted at output
01
h
Voltage signal
output
±10 V
−10.00
−16384
{0.01V}
{1
dec
}
+10.00
16384
S5
Two’s
complement
±0.2 %
2)
3)
Min.
Limit
values
Max.
−12.50 V
−20480
dec
+12.50 V
20480
dec
02
h
Voltage signal
output
+1 ... +5
V
1.0
0
{0.1V}
{1
dec
}
+5.0
16384
S5
Two’s
complement
±0.4 %
2)
3)
Min.
Limit
values
Max.
0.0
−4096
dec
+6.0 V
20480
dec
05
h
Voltage signal
output
0... +10 V 0.0
0
{0.1V}
{1
dec
}
+10.0
16384
S5
Two’s
complement
±0.3 %
2)
3)
Min.
Limit
values
Max.
0.0
0
+12.5 V
20480
dec