Page 304

Parameterising analog modules
Diagnostic data
Parameter setting via system bus (CAN) / CANopen
12.3
12.3.2
L
12.3−6
EDSPM−TXXX−9.0−11/2009
12.3.2
Diagnostic data
If the diagnostic alarm is activated in byte 0 of the parameter data, the diagnostic
data in the emergency telegram are transmitted to the master (see chapter
"Diagnostics", section "Emergency telegram").
8
The following bytes are available for diagnostic data:
Byte
Assignment
0
Bit 0
Module monitoring
0
No fault
1
Module fault
Bit 1
Consistently at 0
Bit 2
External error
0
No error
1
External error
Bit 3
Error at inputs and / or outputs, respectively
0
No error
1
Error at at least one input and / or output, respectively
Bits 4 ... 7
Reserved
1
Bits 0 ... 3
Module type
0101
Analog module
Bit 4
Information on inputs and / or outputs, respectively
0
No information available
1
Information available
2
Reserved
3
Reserved
The following bytes with fixed assignment are available for diagnostic data:
Byte
Assignment
0
Bit 0
Module monitoring
0
No fault
1
Module fault
Bit 1
Reserved
Bit 2
External error
0
No error
1
External error
Bit 3
Error at inputs and / or outputs, respectively
0
No error
1
Error at at least one input and / or output, respectively
Bit 4
Supply error
0
No error
1
No external supply voltage
Bits 5 ... 6
Reserved
Bit 7
Wrong parameters
0
No error
1
Wrong parameters in the module
1
Bits 0 ... 3
Module type
0101
Analog module
Bit 4
Information on inputs and / or outputs, respectively
0
No information available
1
Information available
2
Reserved
3
Reserved
4xanalog input module
4xanalog output module
4xanalog input/output module