7.8 Control terminals
BU 0300 EN
Subject to technical alterations
99
Parameter
Setting value / Description / Note
Supervisor
Parameter set
Available with option
30 = Bus IO In Bit 0 (In combination with option SK TU2-AS1, AS-Interface) *
Closes
31 = Bus IO In Bit 1 (In combination with option SK TU2-AS1, AS-Interface) *
Closes
32 = Bus IO In Bit 2 (In combination with option SK TU2-AS1, AS-Interface) *
Closes
33 = Bus IO In Bit 3 (In combination with option SK TU2-AS1, AS-Interface) *
Closes
34 = Bus IO In Bit 4 (In combination with option SK TU2-AS1, AS-Interface) *
Closes
35 = Bus IO In Bit 5 (In combination with option SK TU2-AS1, AS-Interface) *
Closes
36 = Bus IO In Bit 6 (In combination with option SK TU2-AS1, AS-Interface) *
Closes
37 = Bus IO In Bit 7 (In combination with option SK TU2-AS1, AS-Interface) *
Closes
38 = Value from Bus setpoint
Closes
* Further information on parameterisation with the AS-Interface Æ BU 0090 DE
P435
Relay 1 scalling
P
Always available
-400 ... 400%
[ 100 ]
Adjustment of the limit values of the relay functions. For a negative value, the output function will be
output negative. If the set values are positive the relay contact closes, if they are negative the relay
contact opens when the limit value is reached.
P460 Watchdog
time
Always available
0.0 /
0.1 ... 999.9 s
[ 10.0 ]
0.1 .... 999.9
= The time interval between the expected Watchdog signals (programmable function of
the digital inputs P420 – P425). If this time interval passes without a pulse being registered, a switch
off occurs with an E012 error message.
0.0 = customer fault
: As soon as a low-high flank is registered at the input, the FI switches off with
fault message E012.