7.8 Control terminals

BU 0300 EN

Subject to technical alterations

99

Parameter

Setting value / Description / Note

Supervisor

Parameter set

Available with option




30 = Bus IO In Bit 0 (In combination with option SK TU2-AS1, AS-Interface) *

Closes

31 = Bus IO In Bit 1 (In combination with option SK TU2-AS1, AS-Interface) *

Closes

32 = Bus IO In Bit 2 (In combination with option SK TU2-AS1, AS-Interface) *

Closes

33 = Bus IO In Bit 3 (In combination with option SK TU2-AS1, AS-Interface) *

Closes

34 = Bus IO In Bit 4 (In combination with option SK TU2-AS1, AS-Interface) *

Closes

35 = Bus IO In Bit 5 (In combination with option SK TU2-AS1, AS-Interface) *

Closes

36 = Bus IO In Bit 6 (In combination with option SK TU2-AS1, AS-Interface) *

Closes

37 = Bus IO In Bit 7 (In combination with option SK TU2-AS1, AS-Interface) *

Closes

38 = Value from Bus setpoint

Closes

* Further information on parameterisation with the AS-Interface Æ BU 0090 DE

P435

Relay 1 scalling

P

Always available

-400 ... 400%
[ 100 ]


Adjustment of the limit values of the relay functions. For a negative value, the output function will be
output negative. If the set values are positive the relay contact closes, if they are negative the relay
contact opens when the limit value is reached.

P460 Watchdog

time

Always available

0.0 /
0.1 ... 999.9 s
[ 10.0 ]

0.1 .... 999.9

= The time interval between the expected Watchdog signals (programmable function of

the digital inputs P420 – P425). If this time interval passes without a pulse being registered, a switch
off occurs with an E012 error message.

0.0 = customer fault

: As soon as a low-high flank is registered at the input, the FI switches off with

fault message E012.