Display

Error

Cause

Remedy

Warnings

240

Overwrite data?
Æ YES

NO

These warnings indicate that there is a possibly significant change which
needs additional confirmation.
Once the next procedure has been selected, it must be confirmed with
the "ENTER" key.

241

Delete data?
Æ YES

NO

242

Move SW version?
Æ CONTINUE

CANCEL

243

Move series?
Æ CONTINUE

CANCEL

244

Delete all data?
Æ YES

NO

Inverter control error

250

This function is not enabled

The function requested is not enabled at the frequency inverter
parameter interface.

Change the value of the parameter P509 >Interface< of the

connected frequency inverter to the required function.

251

Control command was not
successful

The control command cannot be implemented by the frequency inverter,
as a higher priority function, e.g. Emergency Stop or an OFF signal to the
control terminals of the frequency inverter, is present

252

Control is not possible
OFFLINE

Call up of a control function in Offline mode.

Change the operating mode of the ParameterBox in the

parameter >Operating Mode< P1302 to Online and repeat
the action.

253

Error acknowledgement not
successful

The acknowledgement of an error at the frequency inverter was not
successful, the error message remains.

Error message from inverter

"Error No.
from
inverter"

Inverter error

"Inverter error text

"

An error has occurred at the frequency inverter with the displayed
number. The frequency inverter error No. and error text is displayed.