List of the possible functions of the digital inputs P420 ... P425, P470
Value
Function
Description
Signal
00
No function
Input switched off.
---
01
Enable right
The FI delivers an output signal with the rotation field right if a
positive setpoint is present. 0
→ 1 Flank (P428 = 0)
High
02
Enable left
The FI delivers an output signal with the rotation field left if a
positive setpoint is present. 0
→ 1 Flank (P428 = 0)
High
If automatic starting is active (P428 = 1), a high level is sufficient.
If the functions "Enable right" and "Enable left" are actuated simultaneously, the FI is blocked.
03
Change rotation direction
Causes the rotation field to change direction, combined with
Enable right or left.
High
04
Fixed frequency 1
1
The frequency from P429 is added to the actual setpoint
value.
High
05
Fixed frequency 2
1
The frequency from P430 is added to the actual setpoint
value.
High
06
Fixed frequency 3
1
The frequency from P431 is added to the actual setpoint
value.
High
07
Fixed frequency 4
1
The frequency from P432 is added to the actual setpoint
value.
High
If several fixed frequencies are actuated at the same time, then they are added with the correct sign. In addition,
the analog setpoint (P400) and possibly the minimum frequency (P104) are added.
08
Parameter set switch Bit 0
Selection of the active parameter set. (Low level = Parameter
set 1, high level = Parameter set 2)
High
09
Hold frequency
During the acceleration or deceleration phase, a low level will
cause the actual output frequency to be "held". A high level
allows the ramp to proceed.
Low
10
Voltage disable
2
The FI output voltage is switched off and the motor runs freely
to a stop (low = blocked).
Low
11
Quick stop
2
The FI reduces the frequency according to the programmed
quick stop time (P426).
Low
12
Fault acknowledgement
2
Fault acknowledgement with an external signal. If this function
is not programmed, an fault can also be acknowledged by a
low enable setting (P506).
0 Æ 1
flank
13
PTC resistor input
2
Analog evaluation of signal present. Switching threshold at
approx. 2.5 V Switch-off delay = 2sec, warning after 1sec.
Analog
14
Remote control
2
With Bus system control, low level switches the control to
control via control terminals.
High
15
Jog frequency
1
The fixed frequency value can be adjusted using the
HIGHER/LOWER and ENTER keys (P113), if control is via
the ControlBox or ParameterBox.
High
16
Motor potentiometer
As in setting 09, however, the frequency is not maintained
below the minimum frequency P104 and above the maximum
frequency P105. The ramps can be set using start-up and
braking time.
Low
17
Reserved
18
Watchdog
2
Input must see a high flank cyclically (P460), otherwise error
E012 will cause a shutdown. Function starts with the 1st high
flank.
0 Æ 1
flank
19
Setpoint 1 on/off
Analog input switch-on and switch-off 1/2 (high = ON) The low
signal sets the analog input to 0% which does not lead to
shutdown when the minimum frequency (P104) > than the
absolute minimum frequency (P505).
High
20
Setpoint 2 on/off
21
Fixed frequency 5
1
The frequency from P433 is added to the actual setpoint value.
High
... continued on the next page