List of the possible functions of the digital inputs P420 ... P425, P470

Value

Function

Description

Signal

00

No function

Input switched off.

---

01

Enable right

The FI delivers an output signal with the rotation field right if a
positive setpoint is present. 0

→ 1 Flank (P428 = 0)

High

02

Enable left

The FI delivers an output signal with the rotation field left if a
positive setpoint is present. 0

→ 1 Flank (P428 = 0)

High

If automatic starting is active (P428 = 1), a high level is sufficient.

If the functions "Enable right" and "Enable left" are actuated simultaneously, the FI is blocked.

03

Change rotation direction

Causes the rotation field to change direction, combined with
Enable right or left.

High

04

Fixed frequency 1

1

The frequency from P429 is added to the actual setpoint
value.

High

05

Fixed frequency 2

1

The frequency from P430 is added to the actual setpoint
value.

High

06

Fixed frequency 3

1

The frequency from P431 is added to the actual setpoint
value.

High

07

Fixed frequency 4

1

The frequency from P432 is added to the actual setpoint
value.

High

If several fixed frequencies are actuated at the same time, then they are added with the correct sign. In addition,
the analog setpoint (P400) and possibly the minimum frequency (P104) are added.

08

Parameter set switch Bit 0

Selection of the active parameter set. (Low level = Parameter
set 1, high level = Parameter set 2)

High

09

Hold frequency

During the acceleration or deceleration phase, a low level will
cause the actual output frequency to be "held". A high level
allows the ramp to proceed.

Low

10

Voltage disable

2

The FI output voltage is switched off and the motor runs freely
to a stop (low = blocked).

Low

11

Quick stop

2

The FI reduces the frequency according to the programmed
quick stop time (P426).

Low

12

Fault acknowledgement

2

Fault acknowledgement with an external signal. If this function
is not programmed, an fault can also be acknowledged by a
low enable setting (P506).

0 Æ 1

flank

13

PTC resistor input

2

Analog evaluation of signal present. Switching threshold at
approx. 2.5 V Switch-off delay = 2sec, warning after 1sec.

Analog

14

Remote control

2

With Bus system control, low level switches the control to
control via control terminals.

High

15

Jog frequency

1

The fixed frequency value can be adjusted using the
HIGHER/LOWER and ENTER keys (P113), if control is via
the ControlBox or ParameterBox.

High

16

Motor potentiometer

As in setting 09, however, the frequency is not maintained
below the minimum frequency P104 and above the maximum
frequency P105. The ramps can be set using start-up and
braking time.

Low

17

Reserved

18

Watchdog

2

Input must see a high flank cyclically (P460), otherwise error
E012 will cause a shutdown. Function starts with the 1st high
flank.

0 Æ 1

flank

19

Setpoint 1 on/off

Analog input switch-on and switch-off 1/2 (high = ON) The low
signal sets the analog input to 0% which does not lead to
shutdown when the minimum frequency (P104) > than the
absolute minimum frequency (P505).

High

20

Setpoint 2 on/off

21

Fixed frequency 5

1

The frequency from P433 is added to the actual setpoint value.

High

... continued on the next page