beautypg.com

NORD Drivesystems BU0300 User Manual

Page 47

background image

3.3 Customer unit overview

BU 0300 EN

Subject to technical alterations

47

3.3.2 Customer unit Standard I/O

(SK CU2-STD, Part. No. 275130020)
(SK CU2-STD-C, Part. No. 275170020)


The Standard I/O Customer Unit provides the highest functionality of digital and
analogue signal processing for the SK 300E. In addition to the standard
equipment, 2 analogue inputs, 4 digital inputs and 1 analogue/digital output are
available.
The 2 analogue inputs are not differential inputs. The analogue inputs can
process signals from 0...10V, 0...20mA or 4...20mA with a burden resistance that
can be switched via a DIP switch. Either analogue or digital evaluation is possible
at the analogue output to transfer actual operating parameters, e.g. to a display
device or process control system.

Note:

AGND, 0V is the reference potential for the analogue and digital inputs.

Customer side


Referen ce voltag e +10 V ( ma x. 10 mA)

[1 1]

AGND / 0V

[1 2]

Ana log inp ut 1

[1 4]

Ana log inp ut 2

[1 6]

Ana log ou tp ut 1

[1 7]

Digital inp ut 2 [Ena ble rig ht]

[2 2]

Digital inp ut 3 [Ena ble left]

[2 3]

Digital inp ut 4 [Para meter se t switch ing]

[2 4]

Digital inp ut 5 [fixed freq uen cy 1]

[2 5]

Sup ply vo lta ge +1 5 V (max. 10 0 mA )

[4 2]

0...10V, 0/4…20mA

or
potentiometer:
2,0k

Ω...10kΩ

Floating contact or
PLC output:

7,5...33V (low=0...3,5V)

(Maximum terminal cross-section: 1,5 mm²)

DIP switches:


You can select, for the analogue input, whether current or voltage setpoints should be used. Set the DIP
switches as follows.

1. Switching the

load resistor

ON = Stromsollwert

0/4...20 mA

for analog input 1

OFF = Spannungssollwert 0...10 V

2. Switching the

load resistor

ON = Current setpoint 0/4...20 mA

for analog input 2

OFF = Voltage setpoint

0...10 V

NOTE

With current setpoint setting:

Scaling must be taken into account when operating with a current setpoint of 0/4...20mA.
If 20mA represents a setting of 100%, then parameter P403 "Analogue input 1 adjustment 100%"
must be set to 5V!
Analogue inputs:
If both analogue inputs are parameterised to the same function, then analogue input 1 has priority
and analogue input 2 has no function!