8 Fault messages
BU 0300 EN
Subject to technical alterations
121
Display
in the ControlBox
Error
text in the Parameter Box
Cause
•
Remedy
Group
Detail in
P700 / P701
E008
8.0
EEPROM parameter loss
(maximum value exceeded) )
Error in EEPROM data
•
Software version of the stored data set not
compatible with the software version of the FI.
NOTE:
Faulty
parameters
are automatically reloaded
(factory setting).
•
EMC interferences (see also E020)
8.1
Invalid inverter type
•
Un-initialised frequency inverter
8.3
EEPROM CIU not recognised
(interface equipment)
EEPROM not present in adapter unit.
•
Switch mains voltage off and on again.
8.4
EEPROM not recognised
internally
EEPROM not present in frequency inverter
• Switch mains voltage off and on again.
8.5
No EEPROM recognised
No EEPROM memory present in system
• Switch mains voltage off and on again.
8.6
Back-up copy used
Internal data used
• Switch mains voltage off and on again.
8.7
Different back-up copy
Internal data overwritten
• Switch mains voltage off and on again.
8.8
Empty EEPROM memory
Un-initialised EEPROM memory
• Switch mains voltage off and on again.
E009
--- ControlBox
error
SPI Bus faulty, no communication with ControlBox.
•
Check ControlBox for correct position.
•
Switch mains voltage off and on again.