7.10 Information
BU 0300 EN
Subject to technical alterations
111
7.10
Information
Parameter
Setting value / Description / Note
Supervisor
Parameter
set
Available with option
P700 Actual
fault
Always available
0 ... 25.5
Actual fault present. Further details in Chapter 8 Error messages.
ControlBox:
Display in numerical code, description of the individual fault numbers can be
found in the point Fault messages.
ParameterBox:
Faults are displayed in plain text, further information can be found in the
point Fault messages.
P701 Last
fault
Always available
0 ... 25.5
This parameter displays the last fault present.
Further details can be found in Chapter 8 fault messages.
P707
... -01
Software version
S
… -02
Always available
0 ... 999.9
This parameter shows the software and revision numbers in the FI. This can be significant when
different FI are assigned the same settings.
... -01
= Version number
... -02
= Revision number
P708
Status of digital inputs
S
Always available
00000000 ...
11111111 (binary)
or
0000 ... 00FF
(hexadecimal)
Displays the status of the digital inputs in binary/hexadecimal code. This display can be used to
check the input signals.
(Dig. input 1-5 = Bit 0-4; signals: 0=low 1=high)
Bit 0 =
Digital input 1
Bit 1 =
Digital input 2
Bit 2 =
Digital input 3
Bit 4 =
Digital input 5
Bit 4 =
Digital input 5
Bit 5 =
Analog input 1
Bit 6 =
Analog input 2
Bit 7 =
Reserved
Bit 7-4
Bit 3-0
Minimum
value
0000
0
0000
0
Binary
hex
Maximum
value
1111
F
1111
F
Binary
hex
ControlBox:
The binary Bits are converted into a hexadecimal value and displayed.
ParameterBox:
The Bits are displayed increasing from right to left (binary).
NOTE:
The customer unit Standard I/O has 4 digital inputs and the Basic I/O has 3
digital inputs.
P709
Voltage analog input 1
S
BSC
STD
0.0 ... 10.0 V
Displays the measured analog input value 1.