7.8 Control terminals
BU 0300 EN
Subject to technical alterations
89
Parameter
Setting value / Description / Note
Supervisor
Parameter
set
Available with option
P405
Analog input function 2
STD
0 ... 16
[ 0 ]
This parameter is identical to P400.
P406
Analog input mode 2
S
STD
0 ... 3
[ 0 ]
This parameter is identical to P401.
P407
Analog input adjustment 2 0%
S
STD
0,0 ... 10.0 V
[ 0.0 ]
This parameter is identical to P402.
P408
Analog input adjustment 2 100%
S
STD
0.0 ... 10.0 V
[ 10.0 ]
This parameter is identical to P403.
P409
Filter analog input 2
S
STD
10 ... 400 ms
[ 100 ]
This parameter is identical to P404.
P410
Minimum frequency auxiliary setpoints
S P
Always available
0.0 ... 400.0 Hz
[ 0.0 ]
The minimum frequency that can act on the setpoint via the auxiliary setpoints.
Auxiliary setpoints are all frequencies that are additionally delivered for further functions in the FI:
Actual frequency PID
Frequency addition
Frequency subtraction
Auxiliary setpoints via BUS
Minimum frequency above analog setpoint (potentiometer)
Process controller
P411
Maximum frequency auxiliary setpoints
S P
Always available
0.0 ... 400.0 Hz
[ 50.0 ]
This is the maximum frequency that can affect the setpoint through the auxiliary setpoints (e.g.
analog input).
Auxiliary setpoints are all frequencies that are additionally delivered for further functions in the FI:
Actual frequency PID
Frequency addition
Frequency subtraction
Auxiliary setpoints via BUS
Maximum frequency above analog setpoint (potentiometer)
Process controller
Further information can be found in the graphic for setpoint processing in Chap. 12.1 !!!
P412
Nominal value Process controller
S P
BSC
STD
0.0 ... 10.0 V
[ 5.0 ]
Fixed specification of a setpoint for the process controller that will only occasionally be altered.
Only with P400 = 14 ... 16 (process controller). Further details can be found in Chap. 12.3