7.8 Control terminals

BU 0300 EN

Subject to technical alterations

89

Parameter

Setting value / Description / Note

Supervisor

Parameter

set

Available with option

P405

Analog input function 2

STD

0 ... 16
[ 0 ]

This parameter is identical to P400.

P406

Analog input mode 2

S

STD

0 ... 3
[ 0 ]

This parameter is identical to P401.

P407

Analog input adjustment 2 0%

S

STD

0,0 ... 10.0 V
[ 0.0 ]

This parameter is identical to P402.

P408

Analog input adjustment 2 100%

S

STD

0.0 ... 10.0 V
[ 10.0 ]

This parameter is identical to P403.

P409

Filter analog input 2

S

STD

10 ... 400 ms
[ 100 ]

This parameter is identical to P404.

P410

Minimum frequency auxiliary setpoints

S P

Always available

0.0 ... 400.0 Hz
[ 0.0 ]

The minimum frequency that can act on the setpoint via the auxiliary setpoints.
Auxiliary setpoints are all frequencies that are additionally delivered for further functions in the FI:

Actual frequency PID

Frequency addition

Frequency subtraction

Auxiliary setpoints via BUS

Minimum frequency above analog setpoint (potentiometer)

Process controller

P411

Maximum frequency auxiliary setpoints

S P

Always available

0.0 ... 400.0 Hz
[ 50.0 ]

This is the maximum frequency that can affect the setpoint through the auxiliary setpoints (e.g.
analog input).
Auxiliary setpoints are all frequencies that are additionally delivered for further functions in the FI:

Actual frequency PID

Frequency addition

Frequency subtraction

Auxiliary setpoints via BUS

Maximum frequency above analog setpoint (potentiometer)

Process controller


Further information can be found in the graphic for setpoint processing in Chap. 12.1 !!!

P412

Nominal value Process controller

S P

BSC

STD

0.0 ... 10.0 V
[ 5.0 ]

Fixed specification of a setpoint for the process controller that will only occasionally be altered.
Only with P400 = 14 ... 16 (process controller). Further details can be found in Chap. 12.3