Parameter

Setting value / Description / Note

Supervisor

Parameter

set

Available with option

P511

USS baud rate

S

Always available

0 ... 3
[ 3 ]

Setting of the transfer rate (transfer speed) via the RS485 interface. All bus participants must have
the same baud rate setting.

0=

4800 baud

1=

9600 Baud

2=

19200 Baud

3=

38400 Baud

P512

USS address

S

Always available

0 ... 30
[ 0 ]

Setting the FI Bus address.

P513 Telegram

timeout

S

Always available

-0.1 ... 100.0 s
[ 0.0 ]

Monitoring function of the active bus interface. Following receipt of a valid telegram, the next one
must arrive within the set period. Otherwise the FI reports an fault and switches off with the fault
message E010 >Bus Time Out<.

-0.1 =

10.8 / 10.2 inactive, monitoring switched off, no error generated

0.0 … 100.0 s =

Response time for telegram failure

P514

CAN baud rate

S

Always available

0 ... 7
[ 4 ]

Used to set the transfer rate (transfer speed) via the CANbus interface. All bus participants must
have the same baud rate setting.
Further information can be obtained from the manual BU 0060 CANbus.

0 = 10kBaud

1 = 20kBaud

2 = 50kBaud

3 = 100kBaud

4 = 125kbaud

5 = 250kBaud

6 = 500kBaud

7 = 1Mbaud *

(test purposes only)

*) Safe operation cannot be guaranteed

P515 CANbus

address

S

Always available

0 ... 255
[ 50 ]

Setting the CANbus address

P516

Skip frequency 1

S P

Always available

0.0 ... 400.0 Hz
[ 0.0 ]

The output frequency is masked off in a range of

± 2Hz around the frequency value set here.

This range is transmitted with the set deceleration and acceleration ramp; it cannot be continuously
supplied to the output. Frequencies below the absolute minimum frequency should not be set.

0=

Masking frequency inactive

P518

Skip frequency 2

S P

Always available

0.0 ... 400.0 Hz
[0.0]

See P516 Masking frequency 1