NORD Drivesystems BU0300 User Manual
Page 104
NORDAC trio SK 300E Manual
104
Subject to technical alterations
BU 0300 EN
Parameter
Setting value / Description / Note
Supervisor
Parameter
set
Available with option
P511
USS baud rate
S
Always available
0 ... 3
[ 3 ]
Setting of the transfer rate (transfer speed) via the RS485 interface. All bus participants must have
the same baud rate setting.
0=
4800 baud
1=
9600 Baud
2=
19200 Baud
3=
38400 Baud
P512
USS address
S
Always available
0 ... 30
[ 0 ]
Setting the FI Bus address.
P513 Telegram
timeout
S
Always available
-0.1 ... 100.0 s
[ 0.0 ]
Monitoring function of the active bus interface. Following receipt of a valid telegram, the next one
must arrive within the set period. Otherwise the FI reports an fault and switches off with the fault
message E010 >Bus Time Out<.
-0.1 =
10.8 / 10.2 inactive, monitoring switched off, no error generated
0.0 … 100.0 s =
Response time for telegram failure
P514
CAN baud rate
S
Always available
0 ... 7
[ 4 ]
Used to set the transfer rate (transfer speed) via the CANbus interface. All bus participants must
have the same baud rate setting.
Further information can be obtained from the manual BU 0060 CANbus.
0 = 10kBaud
1 = 20kBaud
2 = 50kBaud
3 = 100kBaud
4 = 125kbaud
5 = 250kBaud
6 = 500kBaud
7 = 1Mbaud *
(test purposes only)
*) Safe operation cannot be guaranteed
P515 CANbus
address
S
Always available
0 ... 255
[ 50 ]
Setting the CANbus address
P516
Skip frequency 1
S P
Always available
0.0 ... 400.0 Hz
[ 0.0 ]
The output frequency is masked off in a range of
± 2Hz around the frequency value set here.
This range is transmitted with the set deceleration and acceleration ramp; it cannot be continuously
supplied to the output. Frequencies below the absolute minimum frequency should not be set.
0=
Masking frequency inactive
P518
Skip frequency 2
S P
Always available
0.0 ... 400.0 Hz
[0.0]
See P516 Masking frequency 1