Parameter

Setting value / Description / Note

Supervisor

Parameter

set

Available with option

Digital functions:

All relay functions described in Parameter >Function Relay 1< P434 can also be transferred via the
analog output. If a condition has been fulfilled, then there will be 10V at the output terminals.
Negation of the function can be set in parameter >Analog output standardisation< P419.

15 = External brake

16 = Inverter working

17 = Current limit

18 = Torque current limit

19 = Frequency limit

20 = Level with setpoint

21 = Fault

22 = Warning

23 = Overcurrent warning

24 = Overtemperature warning motor

25 = Torque current limit

26 = Value from P541, external control

27 = ... 29 reserved

32 = ... 43 reserved

44 = Bus I/O In Bit 0

45 = Bus I/O In Bit 1

46 = Bus I/O In Bit 2

47 = Bus I/O In Bit 3

48 = Bus I/O In Bit 4

49 = Bus I/O In Bit 5

50 = Bus I/O In Bit 6

51 = Bus I/O In Bit 7

52 = Value from Bus setpoint

P419

Analog output standardisation

P

STD

-500 ... 500 %
[ 100 ]

Analog functions P418 (= 0 ... 14, 30, 31)

Using this parameter an adjustment can be made to the analog output for the selected operating
range. The maximum analog output (10V) corresponds to the standardisation value of the
appropriate selection.
If therefore, at a constant working point, this parameter is raised from 100% to 200%, the analog
output voltage is halved. 10 Volt output signal then corresponds to twice the nominal value.
For negative values the logic is reversed. A setpoint value of 0% will then produce 10V at the
output and -100% will produce 0V.

Digital functions P418 (= 15 ... 28, 34...52)

The switching threshold can be set using this parameter for the functions Current limit (= 17),
Torque current limit (= 18) and Frequency limit (= 19). A value of 100% refers to the corresponding
motor nominal value (see also P435).
With a negative value, the output function is output negated (0/1

→ 1/0).

P420

Digital input function 1

Always available

0 ... 21
[ 13 ]

PTC input

as factory setting, control terminal 21.

Various functions can be programmed. These can be seen in the following table.

NOTE:

Only digital functions are possible with this input, therefore only the functions up to

No. 21!

P421

Digital input function 2

BSC

STD

0 ... 48
[ 1 ]

Enable right

as factory setting, control terminal 22

Various functions can be programmed. These can be seen in the following table.