NORD Drivesystems BU0300 User Manual
Page 141
12 Additional information
BU 0300 EN
Subject to technical alterations
141
Process controller parameter settings
(Example: Setpoint frequency: 50 Hz, control limits: +/-25%)
P105 (maximum frequency) [Hz]
:
[ ]
[ ]
[ ]
⎟
⎠
⎞
⎜
⎝
⎛
×
+
≥
100%
%
P415
Hz
q.
Setpointfr
Hz
q.
Setpointfr
Example:
=
×
+
≥
%
100
%
25
50
50
Hz
Hz
62.5 Hz
P400 (Funct. analog input)
: “4” (frequency addition)
P411 (setpoint frequency) [Hz]
: Set frequency with 10 V at analog input 1
Example: 50 Hz
P412 (Process controller setpoint) : CR middle position / Default setting 5 V (adapt if necessary)
P413 (P controller) [%]
: Factory setting 10% (adapt if necessary)
P414 (I-controller) [% / ms]
: recommended 0.1
ms
%
P415 (limitation +/-) [%]
: Controller limitation (see above)
Note:
In the function process controller, parameter P415 is used as a
controller limiter downstream from the PI controller.
This parameter therefore has a double function.
Example:
25%
of setpoint
P416 (ramp before controller) [s]
: Factory setting 2s (if necessary, adjust to controller behaviour)
P420 (Funct. digital input 1)
: “1” Enable right
P421 (Funct. Digital input 2)
: "40" actual value PID process controller