12 Additional information

BU 0300 EN

Subject to technical alterations

141

Process controller parameter settings


(Example: Setpoint frequency: 50 Hz, control limits: +/-25%)

P105 (maximum frequency) [Hz]

:

[ ]

[ ]

[ ]

×

+

100%

%

P415

Hz

q.

Setpointfr

Hz

q.

Setpointfr

Example:

=

×

+

%

100

%

25

50

50

Hz

Hz

62.5 Hz

P400 (Funct. analog input)

: “4” (frequency addition)

P411 (setpoint frequency) [Hz]

: Set frequency with 10 V at analog input 1

Example: 50 Hz

P412 (Process controller setpoint) : CR middle position / Default setting 5 V (adapt if necessary)

P413 (P controller) [%]

: Factory setting 10% (adapt if necessary)

P414 (I-controller) [% / ms]

: recommended 0.1

ms

%

P415 (limitation +/-) [%]

: Controller limitation (see above)

Note:

In the function process controller, parameter P415 is used as a

controller limiter downstream from the PI controller.

This parameter therefore has a double function.

Example:

25%

of setpoint

P416 (ramp before controller) [s]

: Factory setting 2s (if necessary, adjust to controller behaviour)

P420 (Funct. digital input 1)

: “1” Enable right

P421 (Funct. Digital input 2)

: "40" actual value PID process controller