4.4 Functions of the ParameterBox

BU 0300 EN

Subject to technical alterations

57

Display

After the ParameterBox is connected and the mains voltage for the inverter is switched on, an automatic "Bus
scan"

takes place. The ParameterBox identifies the connected frequency inverter(s). The frequency inverter

type and its actual operating status can be seen in the following display.

300E 0,75kW/3 BSC

1

> NORDAC <

Frequency inverter

ONLINE

U1

P1

EReady

Actual status of

the inverter

Inverter type


In the standard display mode, 3 operating values and the actual frequency inverter status can be displayed
simultaneously.
The operating values displayed can be selected from a list of 8 possible values (in Menu>DisplayValues for
display< P1004).

300E 0,75kW/3 BSC

1

Fi/Hz

U/V

I/A

45.0

190

1.4

ONLINE

U1

P1

R RUNNING

Current actual values for

the selected operating

values and their

applicable units

Current

ParameterBox status

Inverter
selected

Active parameters

in inverter

Actual status of

the inverter

Inverter type

Menu structure level

Customer unit



NOTE

The digital frequency setpoint is factory set to 0Hz. To check whether the motor is working, a

frequency setpoint must be entered with the

key or a jog frequency via the respective menu

level >Parameterise<, >Base parameters< and the respective parameter >Jog frequency< (P113)
Settings must be carried out by qualified personnel only, paying particular attention to safety and
warning instructions.

ATTENTION :

The motor may start immediately after pressing the

START key!