Parameter
Setting value / Description / Note
Supervisor
Parameter
set
Available with option
P413
PID control P-component
S P
BSC
STD
0 ... 400.0 %
[ 10.0 ]
This parameter is only effective when the function PID actual frequency is selected in parameter
P400.
The P-component of the PID controller determines the frequency jump if there is a regulation
deviation based on the rule difference.
For example: At a setting of P413 = 10% and a regulation difference of 50%, 5% is added to the
actual setpoint.
Further information about the PID controller can be found in Chap. 12.2.
P414
PID control P-component
S P
BSC
STD
0 ... 400.0 %/ms
[ 1.0 ]
This parameter is only effective when the function PID actual frequency is selected in parameter
P400.
The I-component of the PID controller determines the frequency change, dependent on time.
Further information about the PID controller can be found in Chap. 12.2.
P415
D-component PID controller
S P
BSC
STD
0 ... 400.0 %ms
[ 1.0 ]
This parameter is only effective when the function PID actual frequency is selected in parameter
P400.
If there is a rule deviation, the D-component of the PID controller determines the frequency change
multiplied by time (%ms).
If one of the analog inputs is set in the function actual value process controller, this parameter
determines the controller limitation (%) after the PI controller.
Further information about the PID controller can be found in Chap. 12.2.
P416
Ramptime PI setpoint
S P
BSC
STD
0.00 ... 99.99 s
[ 2.0 ]
This parameter is only effective when the function PID actual frequency is selected.
Ramp time for the setpoint PID.
Further information about the PID controller can be found in Chap. 12.2.