beautypg.com

NORD Drivesystems BU0300 User Manual

Page 66

background image

NORDAC trio SK 300E Manual

66

Subject to technical alterations

BU 0300 EN

4.6

Error messages of the ParameterBox

Display

Error

Cause

Remedy

Communication error

200

Parameter number
not permissible

These error messages are due to EMC interferences or
differing software versions of the participants.

• Check the software version of the ParameterBox and that

of the connected frequency inverter.

Check the wiring of all components and for possible EMC

interference

201

Parameter value cannot be
changed

202

Parameter outside
value range

203

Incorrect
Sub- Index

204 No

Array

parameter

205

Incorrect parameter type

206

Incorrect response
identifier
USS interface

207

Checksum error of
USS interface

Communication between frequency inverter and ParameterBox is
faulty (EMC), safe operation cannot be guaranteed.

Check the connection to the frequency inverter. Use a

shielded cable between the devices. Route the BUS
leads separately from the motor cables.

208

Incorrect status identifier
USS interface

Communication between frequency inverter and ParameterBox is
faulty (EMC), safe operation cannot be guaranteed.

Check the connection to the frequency inverter. Use a

shielded cable between the devices. Route the BUS
leads separately from the motor cables.

209_1

Inverter not responding

The ParameterBox is waiting for a response from the connected
frequency inverter. The waiting time has elapsed without a response
being received.

Check the connection to the frequency inverter. The

frequency inverter USS parameter settings were changed
during operation.

Identification

error

220 Unknown

device

Device ID not found.
The connected inverter is not listed in the database of the
ParameterBox; no communication can be established.

Please contact your Getriebebau Nord dealership.

221

Software version not
recognised

Software version not found!
The software of the connected frequency inverter is not listed in the
ParameterBox database, no communication can be set up.

Please contact your Nord supply agency.