NORD Drivesystems BU0300 User Manual
Page 67
4.6 Error messages of the ParameterBox
BU 0300 EN
Subject to technical alterations
67
Display
Error
Cause
•
Remedy
222
Inverter extension level not
recognised
An unknown component has been detected in the frequency inverter
(Customer unit).
•
Please check the components installed in the frequency
inverter
•
If necessary, check the software version of the
ParameterBox and the frequency inverter.
223
Bus configuration has
changed
A different device to that saved responds when the last bus
configuration is restored.
This error can only occur if the parameter >Auto. Bus Scan< is set to
OFF
and another device has been connected to the ParameterBox.
•
Activate the Automatic Bus Scan function.
224
Device is not supported
The frequency inverter type connected to the ParameterBox is not
supported!
•
The ParameterBox cannot be used with this frequency
inverter.
225
The connection to the
inverter is blocked
Access to a device that is not ONLINE (previous Time Out
error).
•
Carry out a bus scan via the parameter >Bus Scan<
(P1001).
ParameterBox
operating
error
226
Source and target are
different devices
Copying objects of different types (from / to different inverters) is not
possible.
227
Source is empty
Copying of data from a deleted (empty) storage medium
228
This combination is not
permitted
Target and source for the copying function are the same. The
command cannot be carried out.
229
Object selected is empty
Parameterisation attempt of a deleted storage medium
230 Different
software
versions
Warning
Copying objects with different software versions can lead to problems
when transferring parameters.
231 Invalid
password
Attempt to change a parameter without a valid Box password being
entered in parameter >Box Password< P1306.
232
Bus scan only during
operation: ONLINE
A bus scan (search for a connected frequency inverter) is only possible
when in ONLINE mode.