4.6 Error messages of the ParameterBox

BU 0300 EN

Subject to technical alterations

67

Display

Error

Cause

Remedy

222

Inverter extension level not
recognised

An unknown component has been detected in the frequency inverter
(Customer unit).

Please check the components installed in the frequency

inverter

If necessary, check the software version of the

ParameterBox and the frequency inverter.

223

Bus configuration has
changed

A different device to that saved responds when the last bus
configuration is restored.
This error can only occur if the parameter >Auto. Bus Scan< is set to
OFF

and another device has been connected to the ParameterBox.

Activate the Automatic Bus Scan function.

224

Device is not supported

The frequency inverter type connected to the ParameterBox is not
supported!

The ParameterBox cannot be used with this frequency

inverter.

225

The connection to the
inverter is blocked

Access to a device that is not ONLINE (previous Time Out
error).

Carry out a bus scan via the parameter >Bus Scan<

(P1001).

ParameterBox

operating

error

226

Source and target are
different devices

Copying objects of different types (from / to different inverters) is not
possible.

227

Source is empty

Copying of data from a deleted (empty) storage medium

228

This combination is not
permitted

Target and source for the copying function are the same. The
command cannot be carried out.

229

Object selected is empty

Parameterisation attempt of a deleted storage medium

230 Different

software

versions

Warning

Copying objects with different software versions can lead to problems
when transferring parameters.

231 Invalid

password

Attempt to change a parameter without a valid Box password being
entered in parameter >Box Password< P1306.

232

Bus scan only during
operation: ONLINE

A bus scan (search for a connected frequency inverter) is only possible
when in ONLINE mode.