NORD Drivesystems BU0300 User Manual
Page 120
NORDAC trio SK 300E Manual
120
Subject to technical alterations
BU 0300 EN
Display
in the ControlBox
Error
text in the Parameter Box
Cause
•
Remedy
Group
Detail in
P700 / P701
E003
3.0 Inverter
overcurrent
I
2
t limit has triggered, e.g. > 1.5 x I
n
for 60s
(please also note P504)
•
Avoid continuous overload at FI output
3.1 Overcurrent
chopper
I
2
t limit for brake chopper triggered
•
Avoid overcurrent in braking resistor
E004
4.0 Overcurrent
module
Error signal from module (short duration)
•
Rectify short-circuit or earthing at FI output
•
Use external output choke (motor cable is too long)
E005
5.0 Overvoltage
dc-link
voltage
DC link voltage is too high
•
Reduce energy return by means of a braking resistor
•
Extend deceleration (P103)
•
If necessary, set disconnection mode (P108) with
delay (not for lifting equipment)
•
Extend quick stop time (P426)
5.1 Overvoltage
mains
Mains voltage is too high
•
Please check 380V-20% ... 480V+10%
or 200 ... 240V
± 10%
E006
6.0
DC-Link voltage undervoltage
(charging error)
Inverter mains/link voltage too low
•
Check mains voltage 380V-20% ... 480V+10%
or 200 ... 240V
± 10%
6.1 Mains
undervoltage
E007
7.0
Mains phase failure
One of the three mains input phases was or is interrupted.
•
Check mains phases 380V-20% ... 480V+10%
or 200 ... 240V
± 10%, possibly too low?
•
All three mains phases must be symmetrical.
OFF
NOTE:
OFF appears in the display when the three mains phases are uniformly reduced,
i.e. when a normal mains switch off occurs during operation.