3.2 Technology unit overview

BU 0300 EN

Subject to technical alterations

37

ControlBox functions:

Switching on the frequency inverter. The frequency inverter is now enabled with the set jog frequency
(P113). A preset minimum frequency (P104) may at least be provided. Parameter >Interface< P509
must = 0.

a) To switch off (block) the frequency inverter during operation. The output frequency is reduced to the

absolute minimum frequency (P505) and the frequency inverter shuts down.

b) During parameterisation, the operating value display P000 (starting display after mains ON) can be

called up from any parameter.

7-segment

LED

display

a) Shows the current operating value set during operation (selection in P001) or an error code.
b) During parameterisation, the parameter numbers or the parameter values are shown. When

switched off, but operational, four dashes "_ _ _ _" are displayed or, if a setpoint frequency > 0Hz is
set in P113, this value will flash.

LEDs

1

2

a) The LEDs signal the actual operating parameter set during operation.
b) During

parameterisation, the parameter set being parameterised is displayed.

2

1

= P1

1

2

= P2

a) The motor rotation direction changes when this key is pressed. "Rotation to the left" is indicated by

a minus sign. Attention ! Take care when operating pumps. screw conveyors, ventilators, etc.
Block the key with parameter P540.

b) To cancel a value changed during parameterisation mode, press this key.

a) Press key to increase the frequency.
b) During

parameterisation,

the parameter number or parameter value is increased

a) Press the key to reduce the frequency.
b) During

parameterisation,

the parameter number or parameter value is reduced.

a) Press "ENTER" to store a changed parameter value, or to switch between parameter number and

parameter value.

NOTE:

If a changed value is not to be stored, the

key can be used to exit the parameter without

storing the change.

b) When operating with the keyboard control, the actual frequency value can be saved in parameter

P113 Jog frequency. This is then the starting value when the START key is used to enable.