NORD Drivesystems BU0300 User Manual
Page 122
NORDAC trio SK 300E Manual
122
Subject to technical alterations
BU 0300 EN
Display
in the ControlBox
Error
text in the Parameter Box
Cause
•
Remedy
Group
Detail in
P700 / P701
E010
10.0
Telegram time out
Data transfer is faulty. Check P513.
•
Check external Bus connection.
•
Check Bus Protocol program process.
•
Check Bus master.
•
Check 24V supply of internal CAN/CANopen Bus.
•
Nodeguarding
error (internal CANopen)
•
Bus Off
error (internal CAN Bus)
10.2
External bus module
telegram time-out
Telegram transfer is faulty.
•
Check external connection.
•
Check Bus Protocol program process.
•
Check Bus master.
10.4
External bus module
initialisation failure
• Check
P746.
•
Bus module not correctly plugged in.
•
Check Bus module current supply.
10.1
External Bus module system
failure
Further details can be found in the respective additional BUS
operating instructions.
10.3
10.5
10.6
10.7
10.8
External module
communication failure
Connection fault / error in the external component
E011
11.0
ADU customer unit error
Reference voltage of customer unit faulty (10V/15V). Only
displayed if control is via the control terminals (P509 = 0/1).
•
Check control terminals connection for short-circuit.
E012
12.0
Watchdog customer /
customer error
The Watchdog function is selected at a digital input and the
impulse at the corresponding digital input is not present for
longer than the time set in parameter P460 >Watchdog time<.
E013
13.0
reserved
13.2
Slip error switch-off
monitoring
The slip error monitoring was triggered; the motor could not
follow the setpoint.
•
Increase setting value for torque limit in P112.
•
Check motor data (motor circuit, stator resistor)
E018
18.0 Safety
circuit
The safety circuit triggered while the FI was enabled.
- Still under preparation. -