Display

in the ControlBox

Error

text in the Parameter Box

Cause

Remedy

Group

Detail in
P700 / P701

E010

10.0

Telegram time out

Data transfer is faulty. Check P513.

Check external Bus connection.

Check Bus Protocol program process.

Check Bus master.

Check 24V supply of internal CAN/CANopen Bus.

Nodeguarding

error (internal CANopen)

Bus Off

error (internal CAN Bus)

10.2

External bus module
telegram time-out

Telegram transfer is faulty.

Check external connection.

Check Bus Protocol program process.

Check Bus master.

10.4

External bus module
initialisation failure

• Check

P746.

Bus module not correctly plugged in.

Check Bus module current supply.

10.1

External Bus module system
failure

Further details can be found in the respective additional BUS
operating instructions.

10.3

10.5

10.6

10.7

10.8

External module
communication failure

Connection fault / error in the external component

E011

11.0

ADU customer unit error

Reference voltage of customer unit faulty (10V/15V). Only
displayed if control is via the control terminals (P509 = 0/1).

Check control terminals connection for short-circuit.

E012

12.0

Watchdog customer /
customer error

The Watchdog function is selected at a digital input and the
impulse at the corresponding digital input is not present for
longer than the time set in parameter P460 >Watchdog time<.

E013

13.0

reserved

13.2

Slip error switch-off
monitoring

The slip error monitoring was triggered; the motor could not
follow the setpoint.

Increase setting value for torque limit in P112.

Check motor data (motor circuit, stator resistor)

E018

18.0 Safety

circuit

The safety circuit triggered while the FI was enabled.