beautypg.com

NORD Drivesystems BU0300 User Manual

Page 76

background image

NORDAC trio SK 300E Manual

76

Subject to technical alterations

BU 0300 EN

7.4

Menu groups

There are two switchable parameter data sets available during operation. All parameters can be adjusted
"ONLINE".
The individual parameters are combined in various parameter sets. The first digit of the parameter number
indicates the assignment to a menu group:

Menu group

No.

Main function

Operating displays

(P0--):

For the selection of the physical units of the display value.

Basic parameters

(P1--):

Contain the basic inverter settings, e.g. switch on and switch off
procedures and, along with the motor data, are sufficient for standard
applications.

Motor data / characteristic
curve parameters

(P2--):

Setting of the motor-specific data, important for the ISD current control
and choice of the characteristic curve during the setting of
dynamic and static boost.

Control terminals

(P4--):

Analog input and output scaling, specification of digital input and relay
output functions, as well as PID controller parameters.

Additional parameters

(P5--):

Functions dealing with e.g. the interface, pulse frequency or error
acknowledgement.

Information

(P7--):

For display of e.g. actual operating modes, old error messages, device
status reports or software version (read parameter).

Array parameters

-01


-xx

Some parameters in these groups can be programmed and read in
several levels (arrays). After the parameter is selected, the array level
must also be selected.

Note

Parameter P523 can be used to load the factory settings for all parameters at any time. This can be
helpful, e.g. during the commissioning of a frequency inverter whose parameters no longer
correspond with the factory settings.

Attention

All actual parameter settings will be lost, if P523= 1 is set and confirmed with "ENTER".
Actual parameter settings can be stored by being transferred to the ParameterBox memory or to a
file using the NORD CON software.