7.7

Motor / characteristic curve parameters

Parameter

Setting value / Description / Note

Supervisor

Parameter

set

Available with option

P200 Motor

list

S P

Always available

0 ... 41
[ 0 ]

0 = No change to data

1 = No motor:

In this setting, the FI operates without current control, slip compensation and

pre-magnetising time, and is therefore not recommended for motor applications. Possible
applications are induction furnaces or other applications with coils and transformers. The
following motor data is set here: 50.0Hz / 1500rpm /15.0A / 400V / 0.00kW / cos

ϕ=0.90 /

Star / R

S

0.01

Ω / I

EMPTY

6.5A

2 =

0.18kW 400V

3 =

0.25kW 400V

4 =

0.37kW 400V

5 =

0.55kW 400V

6 =

0.75kW 400V

7 =

1.1kW 400V

8 =

1.5kW 400V

9 =

2.2kW 400V

10 =

3.0kW 400V

11 =

4.0KW 400V

12 =

5.5kW 400V

13 =

7.5kW 400V

14 =

11kW 400V

15 =

0.5Hp 400V

16 =

0.75Hp 400V

17 =

1.0Hp 400V

18 =

1.5Hp 400V

19 =

2.0Hp 400V

20 =

3.0Hp 400V

21 =

5.0Hp 400V

22 =

7.5Hp 400V

23 =

0.25kW 230V

24 =

0.37kW 230V

25 =

0.55kW 230V

26 =

0.75kW 230V

27 =

1.1kW 230V

28 =

1.5kW 230V

29 =

2.2kW 230V

30 =

3.0kW 230V

31 =

4.0kW 230V

32 =

5.5kW 230V

33 =

0.33Hp 230V

34 =

0.5Hp 230V

35 =

0.75Hp 230V

36 =

1.0Hp 230V

37 =

1.5Hp 230V

38 =

2.0Hp 230V

39 =

3.0Hp 230V

40 =

4.0Hp 230V

41 =

7.5Hp 230V

With this parameter, the motor data presets can be changed. The factory setting in parameters P201
- P209 is a 4-pole DC standard motor with the nominal FI power.
Select one of the possible digits and press the ENTER key to set all of the following motor
parameters (P201 to P209). The motor data is based on 4-pole DC standard motors.

NOTE:

As P200 returns to = 0 after the input confirmation, the control of the set motor can be

implemented via parameter P205.

P201 Nominal

frequency

S P

Always available

20.0 ... 400.0 Hz
[***]

The nominal frequency determines the v/f break point at which the FI supplies the nominal frequency
(P204) at the output.

P202 Nominal

speed

S P

Always available

300..24000 rpm
[***]

The nominal speed is important for the correct calculation and control of the motor slip and the speed
display (P001 = 1).









*** These settings are dependent on the selection in parameter 200.