7.7
Motor / characteristic curve parameters
Parameter
Setting value / Description / Note
Supervisor
Parameter
set
Available with option
P200 Motor
list
S P
Always available
0 ... 41
[ 0 ]
0 = No change to data
1 = No motor:
In this setting, the FI operates without current control, slip compensation and
pre-magnetising time, and is therefore not recommended for motor applications. Possible
applications are induction furnaces or other applications with coils and transformers. The
following motor data is set here: 50.0Hz / 1500rpm /15.0A / 400V / 0.00kW / cos
ϕ=0.90 /
Star / R
S
0.01
Ω / I
EMPTY
6.5A
2 =
0.18kW 400V
3 =
0.25kW 400V
4 =
0.37kW 400V
5 =
0.55kW 400V
6 =
0.75kW 400V
7 =
1.1kW 400V
8 =
1.5kW 400V
9 =
2.2kW 400V
10 =
3.0kW 400V
11 =
4.0KW 400V
12 =
5.5kW 400V
13 =
7.5kW 400V
14 =
11kW 400V
15 =
0.5Hp 400V
16 =
0.75Hp 400V
17 =
1.0Hp 400V
18 =
1.5Hp 400V
19 =
2.0Hp 400V
20 =
3.0Hp 400V
21 =
5.0Hp 400V
22 =
7.5Hp 400V
23 =
0.25kW 230V
24 =
0.37kW 230V
25 =
0.55kW 230V
26 =
0.75kW 230V
27 =
1.1kW 230V
28 =
1.5kW 230V
29 =
2.2kW 230V
30 =
3.0kW 230V
31 =
4.0kW 230V
32 =
5.5kW 230V
33 =
0.33Hp 230V
34 =
0.5Hp 230V
35 =
0.75Hp 230V
36 =
1.0Hp 230V
37 =
1.5Hp 230V
38 =
2.0Hp 230V
39 =
3.0Hp 230V
40 =
4.0Hp 230V
41 =
7.5Hp 230V
With this parameter, the motor data presets can be changed. The factory setting in parameters P201
- P209 is a 4-pole DC standard motor with the nominal FI power.
Select one of the possible digits and press the ENTER key to set all of the following motor
parameters (P201 to P209). The motor data is based on 4-pole DC standard motors.
NOTE:
As P200 returns to = 0 after the input confirmation, the control of the set motor can be
implemented via parameter P205.
P201 Nominal
frequency
S P
Always available
20.0 ... 400.0 Hz
[***]
The nominal frequency determines the v/f break point at which the FI supplies the nominal frequency
(P204) at the output.
P202 Nominal
speed
S P
Always available
300..24000 rpm
[***]
The nominal speed is important for the correct calculation and control of the motor slip and the speed
display (P001 = 1).
*** These settings are dependent on the selection in parameter 200.