7.9 Additional parameters

BU 0300 EN

Subject to technical alterations

103

Parameter

Setting value / Description / Note

Supervisor

Parameter

set

Available with option

P506

Automatic fault acknowledgement

S

Always available

0 ... 7
[ 0 ]

In addition to the manual error acknowledgement, an automatic one can also be selected.

0= No

automatic

error acknowledgement

1...5 =

Number of permissible automatic error acknowledgments within one mains-on cycle. If the

mains are switched off and then on, the full number will be available again.

6= Always

, an error message will always be automatically acknowledged when the cause is no

longer present.

7= ENTER

key,

acknowledgement is only possible using the ENTER key or by mains switch-

off. No acknowledgement is implemented by removing the enable!

P507 PPO

type

S

Always available

1 ... 4
[ 1 ]

This parameter can only be used with the technology units Profibus, DeviceNet or InterBus

See also additional descriptions BU 0020, BU 0080, BU 0070

P508 Profibus

address

S

Always available

1 ... 126
[ 1 ]

Profibus address, only with the technology unit Profibus

See also the additional description for the Profibus control BU 0020

P509 Interface

S

Always available

0 ... 20
[ 0 ]

Selection of the interface via which the FI is controlled. (P503 Master function output)

0=

Control terminals or keyboard control

** with the ParameterBox, ControlBox,

Potentiometer option or the Bus I/O Bits.

1=

Only control terminals

*

, the FI can only be controlled via the digital and analog input

signals or via the Bus I/O Bits.

2= USS

setpoint

*

, the frequency setpoint is transferred via the RS485 interface. Control via

the digital inputs is still active.

3=

USS control word *,

the control signals (enable, rotation direction, etc.) are transferred via

the RS485 interface, the setpoint via the analog input or the fixed frequencies.

4= USS

*

, all control data is transferred via the RS485 interface. The analog and digital inputs

have no function.

5= CAN

setpoint

*

6=

CAN control word

*

7= CAN

*

8= Profibus

setpoint

*

9= Profibus

control

word

*

10= Profibus

*

11= CAN

Broadcast

*

12= Interbus

setpoint

*

13= InterBus

control

word

*

14= Interbus

*

15=

CAN Open setpoint

*

16=

CAN Open control word

*

17= CAN

Open

*

18= DeviceNet

setpoint

*

19= DeviceNet

control

word

*

20= DeviceNet

*

NOTE:
For details about the respective Bus systems: please
refer to the respective Options descriptions.

BU 0020 = Profibus

BU 0050 = USS

BU 0060 = CANopen

BU 0070 = InterBus

BU 0080 = DeviceNet

BU 0090 = AS-Interface

*) The keyboard control (ParameterBox, ControlBox,
Potentiometer option) is blocked, parameterisation is
still possible.

**) If the communication during keyboard control is
interrupted (time out 0.5 sec), the FI will block without
error message.