NORDAC trio SK 300E Manual

46

Subject to technical alterations

BU 0300 EN

3.3.1 Customer unit Basic I/O

(SK CU2-BSC, Part. No. 275130010)
(SK CU2-BSC-C, Part. No. 275170010)


The Basic I/O customer unit (Customer Unit) provides an adequate number of
control signals for simple control tasks, thereby offering a budget solution for
many cases.

In addition to the controls available in the standard version, the Basic I/O has
one analogue and 3 digital inputs. The analogue differential input can handle
signals from 0...10V, 0...20mA or 4...20mA.

Note:

AGND, 0V is the reference potential for the analogue and digital

inputs.

Customer

side

Reference voltage +10 V (max. 10 mA)

[11]

AGND, 0V

[12]

Analog input -

[13]

Analog input +

[14]

Digital input 2 [Enable right]

[22]

Digital input 3 [Enable left]

[23]

Digital input 4 [Parameter set switching] [24]
Supply voltage +15 V (max. 100 mA)

[42]

0...10V, 0/4…20mA
or
potentiometer:
2,0k

Ω...10kΩ

Floating contacts or
output of a PLC:
7,5...33V (low=0...3,5V)

(Maximum terminal cross-section: 1,5 mm²)

DIP switches:


You can select whether current or voltage setpoints should be used for the analogue input. Set the DIP
switches as follows.

1. Switching the

load resistor for

ON = Current setpoint

0/4...20 mA

analog input 1

OFF = Voltage setpoint

0...10 V

2. Switching a bridge between

ON = Bridge closed

terminals AGND/0V and AIN-

OFF = Bridge open


NOTE

With current setpoint setting:

Scaling must be taken into account when operating with a current setpoint of 0/4...20mA.
If 20mA represents a setting of 100%, then parameter P403 "Analog input 1 adjustment 100%" must
be set to 5V!