NORDAC trio SK 300E Manual

112

Subject to technical alterations

BU 0300 EN

Parameter

Setting value / Description / Note

Supervisor

Parameter

set

Available with option

P710

Voltage analog output 1

S

STD

0.0 ... 10.0 V

Displays the output value of the analog output 1.

P711

State of Relays

S

Always available

00 ... 11
(binary)

Displays the actual status of the signal relay. 00 ... 11 (binary); Bit 0 = Relay 1 (P434)

P712

Voltage analog input 2

S

STD

0.0 … 10.0 V

Displays the measured analog input value 2.

P716 Current

frequency

S

Always available

-400.0...400.0 Hz

Displays the current output frequency.

P717 Current

speed

S

Always available

0 ... 9999 rpm

Displays the current motor speed calculated by the FI.

NOTE:

Positive values are displayed for both rotation directions.

P718

... -01

... -02

... -03

Current setpoint frequency

S

Always available

-400.0...400.0 Hz

Displays the frequency specified by the setpoint.

... -01

= Actual setpoint frequency from the setpoint source

... -02

= Actual setpoint frequency after processing in the FI status machine

... -03

= Actual setpoint frequency after frequency ramp

P719 Actual

current

S

Always available

0 ... 50.0 A

Displays the actual output current.

P720

Actual torque current

S

Always available

-50.0 ... 50.0 A

Displays the actual calculated torque developing output current (active current). Basis for
calculation are the motor data P201 ... P209.
(Positive value = motor operation; Negative value – generator operation)

P722 Actual

voltage

S

Always available

0 ... 1000 V

Displays the actual voltage supplied by the FI output.

P728 Input

voltage

S

Always available

0 ... 1000 V

Displays the current mains voltage at the FI input.