8 Fault messages

BU 0300 EN

Subject to technical alterations

119

8 Fault messages

Faults cause the frequency inverter to switch off. This prevents device defects.

The following options are available to reset an fault (acknowledge):

1. By switching the mains off and on again,
2. By an appropriately programmed digital input (P420 ... P424 = function 12),
3. By removing the "enable" from the FI (if no digital input acknowledge has been programmed),
4. By Bus acknowledgement or
5. by P506, the automatic fault acknowledgement.

Device LEDs:

In the delivery condition (without technology unit), 2 LEDs

(green/red) are visible externally (see illustration). These indicate the
actual status of the device.

The

green LED

indicates that the mains voltage is present and

operational, while a flashing code that increases in speed shows the
degree of overload at the frequency inverter output.

The

red LED

signals actual error by flashing with a frequency which

corresponds to the number code of the fault (Section. 6.2).

8.1

ControlBox display

The ControlBox displays an error with its number and the prefix "E". In addition, the actual error is displayed
in parameter P700. The last error messages are stored in parameter P701.
If the cause of the fault is no longer present, the error display in the ControlBox flashes and the fault can be
acknowledged with the Enter key.

8.2

Table of possible error messages

Display

in the ControlBox

Error

text in the Parameter Box

Cause

Remedy

Group

Detail in
P700 / P701

E001

1.0 Inverter

overtemperature

Error signal from output stage module (static)

Reduce ambient temperature (<50°C or <40°C , see
also Chap. 9 Technical data)

E002

2.0

Overtemperature

motor

(PTC)
Only if a digital input is
programmed (Function 13).

Motor temperature sensor has triggered

Reduce motor load

Increase motor speed

Use motor external fan

2.1

Motor overtemperature

(I

2

t)

Only if I

2

t - Motor (P535) is

programmed.

I

2

t - Motor has triggered

Reduce motor load

Increase motor speed