NORDAC trio SK 300E Manual

78

Subject to technical alterations

BU 0300 EN


7.5

Operating displays

The abbreviation FI will be used below for frequency inverter.

Parameter

Setting value / Description / Note

Supervisor

Parameter set

Available with option

P001

Selection display

Always available

0 ... 6
[ 0 ]

0 =

Actual frequency [Hz], the frequency currently supplied by the FI.

1 =

Speed [1/min], the actual speed calculated by the FI

2 =

Set frequency [Hz], the output frequency equivalent to the actual setpoint. This need not match
the actual output frequency.

3 =

Current [A], the actual output current measured by the FI.

4 =

Torque current [A], the torque-developing output current of the FI.

5 =

Voltage [Vac], the actual alternating voltage being output by the FI.

6 =

Link voltage [Vdc], the FI-internal link voltage.

P003

Supervisor mode

Always available

0 ... 9999

[ 0 ]

Supervisor mode can be switched on and off here. The number of visible parameters when the
supervisor mode is switched off is dependent on the use of a ParameterBox or ControlBox.

0 = Supervisor Mode switched off

(only limited number of parameters are visible)

1 = Supervisor mode switched on

(all parameters are visible (P001 – P746)

2 = Only the menu group 0

> Operating display< (P001 … P003) is visible.

3… 9999, like setting value 2.

Visible parameters:
Supervisor mode switched off

Æ limited number

ParameterBox (SK TU2-PAR-…)

ControlBox (SK TU2-CTR)

P001

Selection of the operating display

P003 Supervisor

mode

P001

Selection of the operating display

P003 Supervisor

mode

P102

Acceleration time

P103 Deceleration

time

P104 Minimum

frequency

P105 Maximum

frequency

P107

Brake reaction time

P400

Analog input function 1 (only with STD

or

STD)

P405

Analog input function 2 (only with STD)

P418

Analog output function (only with STD)

P419

Analog output scalling (only with STD)

P420

Digital input function 1

P421

Digital input function 2 (only with BSC

or

STD)

P422

Digital input function 3 (only with BSC

or

STD)

P423

Digital input function 4 (only with BSC

or

STD)

P424

Digital input function 5 (only with STD)

P434 Function

relay

1

P435

Relay 1 scalling

P460 Time

watchdog

P700 Actual

error

P701 Last

fault

P743 Inverter

ID

P744 Configuration