7.5
Operating displays
The abbreviation FI will be used below for frequency inverter.
Parameter
Setting value / Description / Note
Supervisor
Parameter set
Available with option
P001
Selection display
Always available
0 ... 6
[ 0 ]
0 =
Actual frequency [Hz], the frequency currently supplied by the FI.
1 =
Speed [1/min], the actual speed calculated by the FI
2 =
Set frequency [Hz], the output frequency equivalent to the actual setpoint. This need not match
the actual output frequency.
3 =
Current [A], the actual output current measured by the FI.
4 =
Torque current [A], the torque-developing output current of the FI.
5 =
Voltage [Vac], the actual alternating voltage being output by the FI.
6 =
Link voltage [Vdc], the FI-internal link voltage.
P003
Supervisor mode
Always available
0 ... 9999
[ 0 ]
Supervisor mode can be switched on and off here. The number of visible parameters when the
supervisor mode is switched off is dependent on the use of a ParameterBox or ControlBox.
0 = Supervisor Mode switched off
(only limited number of parameters are visible)
1 = Supervisor mode switched on
(all parameters are visible (P001 – P746)
2 = Only the menu group 0
> Operating display< (P001 … P003) is visible.
3… 9999, like setting value 2.
Visible parameters:
Supervisor mode switched off
Æ limited number
ParameterBox (SK TU2-PAR-…)
ControlBox (SK TU2-CTR)
P001
Selection of the operating display
P003 Supervisor
mode
P001
Selection of the operating display
P003 Supervisor
mode
P102
Acceleration time
P103 Deceleration
time
P104 Minimum
frequency
P105 Maximum
frequency
P107
Brake reaction time
P400
Analog input function 1 (only with STD
or
STD)
P405
Analog input function 2 (only with STD)
P418
Analog output function (only with STD)
P419
Analog output scalling (only with STD)
P420
Digital input function 1
P421
Digital input function 2 (only with BSC
or
STD)
P422
Digital input function 3 (only with BSC
or
STD)
P423
Digital input function 4 (only with BSC
or
STD)
P424
Digital input function 5 (only with STD)
P434 Function
relay
1
P435
Relay 1 scalling
P460 Time
watchdog
P700 Actual
error
P701 Last
fault
P743 Inverter
ID
P744 Configuration