Parameter

Setting value / Description / Note

Supervisor

Parameter set

Available with option

P434

Function relay 1

P

Always available

0 ... 38
[7]

Control terminals 1/2:

The settings 3 to 5 and 11 work with 10% hysteresis, i.e. the relay contact closes (function 11 opens)
when the limit value is reached and opens (function 11 closes) when a 10% smaller value is
undershot. This behaviour can be inverted with a negative value in P435.

Setting / Function

Relay contact ...

for limit value

or function

0 = No

function

Open

1 = External

brake

, to control a brake on the motor. The relay switches at the

set absolute minimum frequency (P505, default: 2 Hz). A setpoint delay
should be programmed for typical brakes (see P107).

NOTE:

In the SK 300E, a DC voltage is generated for a brake and

supplied at the terminals -Br and +Br. The relay contact should generally
be used with a special brake voltage.

Closes

2 = Inverter

is

working

, the closed relay contact indicates voltage at the FI

output (U - V - W).

Closes

3 = Current

limit

*, based on the setting of the motor nominal current in P203.

This value can be adjusted with the standardisation (P435).

Closes

4 = Torque current limit *, based on motor data settings in P203 and P206.

Signals a corresponding torque load. This value can be adjusted with the
standardisation (P435).

Closes

5 = Frequency limit *, based on motor nominal frequency setting in P201.

This value can be adjusted with the standardisation (P435).

Closes

6 = Level

with

Setpoint,

indicates that the FI has completed the frequency

increase or decrease. Setpoint frequency = actual frequency! After the
contact is closed, the setpoint must change by at least 1 Hz.

Æ

Setpoint not reached - contact opens

Closes

7 = Fault, general Fault message. Fault is or not yet acknowledged.

Æ

Operational - contact closes

Opens

8 = Warning:

general warning, a limit value was reached that could lead to a

later shutdown of the FI.

Opens

9 = Overcurrent

warning

: At least 130% FI nominal current was delivered for

30 sec. (l

2

t function)

Opens

10 = Overtemperature motor (warning): The motor temperature is evaluated

via a digital input. Æ Motor is too hot. Warning occurs after 1 second,
overheating switch off after 2 seconds.

Opens

11 = Torque current limit/ current limit active (warning), limit value in P112

is reached. P435 has no significance. Hysteresis = 10%.

Opens

12 = Value of P541 - External control: The relay can be controlled using

parameter P541 (Bit 0), independently of the actual operating status of
the FI.

Closes

13 = … 29 reserved

---