Parameter

Setting value / Description / Note

Supervisor

Parameter

set

Available with option

P402

Analog input adjustment 1 0%

S

BSC

STD

0.0 ... 10.0 V
[ 0.0 ]

This parameter sets the voltage that should correspond with the minimum value of the selected
function for the analog input 1.
In the factory setting (setpoint) this value is equivalent to the setpoint set via P104 >Minimum
frequency<.
Typical setpoints and corresponding settings:

0 - 10V

Æ

0.0

V

2 - 10 V

Æ

2.0 V (monitored with the function 0-10V)

0 - 20 mA

Æ

0.0 V (internal resistance approx. 250

Ω)

4 - 20 mA

Æ

1.0 V (internal resistance approx. 250

Ω)

P403

Analog input adjustment 1 100%

S

BSC

STD

0.0 ... 10.0 V
[ 10.0 ]

This parameter sets the voltage that should correspond with the maximum value of the selected
function for the analog input 1.
In the factory setting (setpoint) this value is corresponds with the setpoint set via P105 >Maximum
frequency<.
Typical setpoints and corresponding settings:

0 - 10 V

Æ

10.0

V

2 - 10 V

Æ

10.0 V (monitored with the function 0-10V)

0 - 20 mA

Æ

5.0 V (internal resistance approx. 250

Ω)

4 - 20 mA

Æ

5.0 V (internal resistance approx. 250

Ω)

P400 … P403

P401 = 0 Æ 0 – 10V limited

0.0V

2.5V

5.0V

10.0V

P105

P104

P402

P403

Output

frequency

Setpoint

voltage

positive

P401 = 1 Æ 0 - 10V not limited

0.0V

2.5V

5.0V

10.0V

P105

P104

P402

P403

Output

frequency

Setpoint

voltage

positive

negative

P404

Filter analog input 1

S

BSC

STD

10 ... 400 ms
[ 100 ]

Adjustable digital low-pass filter for the analog signal.
Interference peaks are hidden, the reaction time is extended.