Parameter
Setting value / Description / Note
Supervisor
Parameter
set
Available with option
P402
Analog input adjustment 1 0%
S
BSC
STD
0.0 ... 10.0 V
[ 0.0 ]
This parameter sets the voltage that should correspond with the minimum value of the selected
function for the analog input 1.
In the factory setting (setpoint) this value is equivalent to the setpoint set via P104 >Minimum
frequency<.
Typical setpoints and corresponding settings:
0 - 10V
Æ
0.0
V
2 - 10 V
Æ
2.0 V (monitored with the function 0-10V)
0 - 20 mA
Æ
0.0 V (internal resistance approx. 250
Ω)
4 - 20 mA
Æ
1.0 V (internal resistance approx. 250
Ω)
P403
Analog input adjustment 1 100%
S
BSC
STD
0.0 ... 10.0 V
[ 10.0 ]
This parameter sets the voltage that should correspond with the maximum value of the selected
function for the analog input 1.
In the factory setting (setpoint) this value is corresponds with the setpoint set via P105 >Maximum
frequency<.
Typical setpoints and corresponding settings:
0 - 10 V
Æ
10.0
V
2 - 10 V
Æ
10.0 V (monitored with the function 0-10V)
0 - 20 mA
Æ
5.0 V (internal resistance approx. 250
Ω)
4 - 20 mA
Æ
5.0 V (internal resistance approx. 250
Ω)
P400 … P403
P401 = 0 Æ 0 – 10V limited
0.0V
2.5V
5.0V
10.0V
P105
P104
P402
P403
Output
frequency
Setpoint
voltage
positive
P401 = 1 Æ 0 - 10V not limited
0.0V
2.5V
5.0V
10.0V
P105
P104
P402
P403
Output
frequency
Setpoint
voltage
positive
negative
P404
Filter analog input 1
S
BSC
STD
10 ... 400 ms
[ 100 ]
Adjustable digital low-pass filter for the analog signal.
Interference peaks are hidden, the reaction time is extended.