7.8 Control terminals

BU 0300 EN

Subject to technical alterations

93

Parameter

Setting value / Description / Note

Supervisor

Parameter

set

Available with option

P422

Digital input function 3

BSC

STD

0 ... 48
[ 2 ]

Enable left

as factory setting, control terminal 23

Various functions can be programmed. These can be seen in the following table.

P423

Digital input function 4

BSC

STD

0 ... 48
[ 8 ]

Parameter set switching Bit 0

as factory setting, control terminal 24

Various functions can be programmed. These can be seen in the following table.

P424

Digital input function 5

STD

0 ... 48
[ 4 ]

Fixed frequency 1

(P429) as factory setting, control terminal 25

Various functions can be programmed. These can be taken from the following table.