Xl™ series – Xylem XL Series H-522 - Plus User Manual
Page 137

XL™ Series
SDI-12 Operations 14-21
Response to a "aM!" command: (when the system is set to factory defaults)
Command
Response
Time Values
Description
-------------
---------------------
------- --------
-------------------------------
"aM!"
"a0063
6 sec
3
Initiate pressure and temperature
measurement
Subsequent Command
Response
--------------------------- ------------------------------------
"aD0!"
a+xxx.xxx+yyy.yyy+zz.z
Key
Description
Units
-------------
-------------------------
-----------------------------------
xxx.xxx
Current Stage
Feet (Default)
yyy.yyy Current Pressure
Pounds-per-Square Inch (PSI)
zz.z
Current Temperature
Centigrade (EC)
Note: The number of parameters returned and their order, can be modified by the user.
Response to a "aM1!" command:
Command
Response
Time Values
Description
-------------
---------------------
------- --------
-----------------------------
"aM1!"
"a0084
8 sec 4
Initiate diagnostic pressure and
temperature measurement
Subsequent Command
Response
--------------------------- --------------------------------------------------------
"aD0!"
a+xxx.xxx+yy.y+XXXXXX+YYYYYY
Key
Description
Units
-------------
-------------------------
-----------------------------------
xxx.xxx
Current Pressure
Pounds-per-Square Inch (PSI)
yy.y
Current Temperature
Centigrade (EC)
XXXXXX
Current Pressure
Raw Reading
YYYYYY
Current Temperature
Raw Reading
H-350XL™ Supported Measurement Commands:
14.7.6 Initiate Verify Command
The Verify Command causes a verify sequence to be performed. The result of this command is