Integrations with Other Applications
MC/ServiceGuard Integration
Chapter 13
635
•
SERVICE_NAME
,
SERVICE_FAIL_FAST_ENABLED
,
SERVICE_HALT_TIMEOUT
Enter the service information. For the service name, you can enter
any name but note that you will use the same name in the control
file afterwards. For example:
SERVICE_NAME omni_sv
SEVICE_FAIL_FAST_ENABLED NO
SERVICE_HALT_TIMEOUT 300
•
SUBNET
Enter the subnet of the cluster. For example:
SUBNET 10.17.0.0
8. Modify the Data Protector package control file (for example,
/etc/cmcluster/ob2cl/ob2cl.cntl
). Refer to the example of this
file in “Example of the Package Control File” on page A-38.
In this file, modify the following fields:
Modifying the
Control File
•
VG [n]
Specify the volume group used by this package. For example:
VG [0] = /dev/vg_ob2cm
•
LV [n]
,
FS [n]
,
FS_MOUNT_OPT [n]
Specify the logical volume and filesystem mount information:
LV [0] = /dev/vg_ob2cm/lv_ob2cm
FS [0] = /omni_shared
FS_MOUNT_OPT[0]=” ”
•
IP
,
SUBNET
Specify the IP and the subnet information used by this package.
For example:
IP [0] = 10.17.3.230
SUBNET [0] = 10.17.0.0
•
SERVICE_NAME
,
SERVICE_CMD
,
SERVICE_RESTART
Specify the service name, command, and restart parameters.