Copying parameters, Related parameters – Yaskawa Matrix Converter User Manual
Page 293
![background image](https://www.manualsdir.com/files/819680/content/doc293.png)
6
-128
Copying Parameters
The digital operator can perform the following three functions using the built-in EEPROM (non-volatile mem-
ory).
•
Store MxC parameter set values in the digital operator (READ)
•
Write parameter set values stored in the digital operator to the MxC (COPY)
•
Compare parameter set values stored in the digital operator with MxC parameters (VERIFY)
Related Parameters
IMPORTANT
The Matrix Converter is displayed as MxC, and the digital operator is displayed as OP while executing the
COPY function.
Parameter
Number
Name
Description
Setting
Range
Default
Change
during
Run
Control Methods
Display
V/f
Open
Loop
Vector
Flux
Vector
o3-01
Copy Function
Selection
This parameter controls the copying of
parameters to and from the digital operator.
0: COPY SELECT (no function)
1: INV → OP READ: All parameters are
copied from the MxC to the digital opera-
tor.
2: OP → INV WRITE: All parameters are
copied from the digital operator to the
MxC.
3: OP⇔INV VERIFY: Parameter settings in
the MxC are compared to those in the dig-
ital operator.
Note: When using the copy function, the MxC
model number (o2-04), software num-
ber (U1-14), and control method (A1-
02) must match or an error will occur.
0 to 3
0
No
A
A
A
Copy Function Sel
o3-02
Copy Allowed
Selection
Enables and disables the digital operator copy
functions.
0: Disabled. - No digital operator copy func-
tions are allowed.
1: Enabled. - Copying allowed.
0 or 1
0
No
A
A
A
Read Allowable