Yaskawa Matrix Converter User Manual
Page 135
Parameter Tables
5-
35
* The defaults in the parentheses are for 3-wire sequence.
Multi-Function Contact Input Functions
H1-09
Multi-Function
Digital Input Ter-
minal S11 Func-
tion Selection
Multi-function contact input 9
0 to 78
7
No
A
A
A
408H
-
Terminal S11 Sel
H1-10
Multi-Function
Digital Input Ter-
minal S12 Func-
tion Selection
Multi-function contact input 10
0 to 78
15
No
A
A
A
409H
-
Terminal S12 Sel
Set
Value
Function
Control
Methods
Page
V/f
Open
Loop
Vector
Flux
Vector
0
3-wire sequence (Forward/Reverse Run Command)
Yes
Yes
Yes
6-9
1
Local/Remote selection (ON: Operator, off: Parameter setting)
Yes
Yes
Yes
6-67
2
Option/MxC selection (ON: Option card)
Yes
Yes
Yes
6-74
6-141
3
Multi-step speed reference 1
When H3-09 (Multi-function analog input (terminal A2) function selection) is set to
0 (Auxiliary frequency reference), this function can be used with the master/auxiliary
speed switch.
Yes
Yes
Yes
6-5
4
Multi-step speed reference 2
Yes
Yes
Yes
6-5
5
Multi-step speed reference 3
Yes
Yes
Yes
6-5
6
Jog Frequency Command (higher priority than multi-step speed reference)
Yes
Yes
Yes
6-5
7
Accel/decel time 1
Yes
Yes
Yes
6-18
8
External baseblock NO (NO contact: Baseblock at on)
Yes
Yes
Yes
6-68
9
External baseblock NC (NC contact: Baseblock at off)
Yes
Yes
Yes
6-68
A
Accel/decel ramp hold (ON: Accel/decel stopped, frequency on hold)
Yes
Yes
Yes
6-69
B
OH2 alarm signal input (ON: OH2 will be displayed)
Yes
Yes
Yes
-
C
Multi-function analog input selection (ON: Enable)
Yes
Yes
Yes
-
E
Speed control integral reset (ON: Integral control disabled)
No
No
Yes
6-116
F
Not used (Set when a terminal is not used)
-
-
-
-
10
Up Command (Always set with the Down Command)
Yes
Yes
Yes
6-70
11
Down Command (Always set with the Up Command)
Yes
Yes
Yes
6-70
12
FJOG Command (ON: Forward run at jog frequency d1-17)
Yes
Yes
Yes
6-75
13
RJOG Command (ON: Reverse run at jog frequency d1-17)
Yes
Yes
Yes
6-75
14
Fault reset (Reset when turned on)
Yes
Yes
Yes
7-2
15
Emergency stop (Normally open condition: Decelerate to stop in deceleration time
set in C1-09 when on).
Yes
Yes
Yes
6-16
16
Motor Switch Command (Motor 2 selection)
Yes
Yes
Yes
-
17
Emergency stop (Normally closed condition: Decelerate to stop in deceleration time
set in C1-09 when off)
Yes
Yes
Yes
6-16
Parameter
Number
Name
Description
Setting
Range
Default
Change
during
Run
Control
Methods
MEMO-
BUS
Register
Page
Display
V/f
Open
Loop
Vector
Flux
Vector