Acceleration and Deceleration Characteristics
6-
17
Acceleration and Deceleration Characteristics
This section explains the acceleration and deceleration characteristics of the MxC.
Setting Acceleration and Deceleration Times
The “acceleration time” refers to the time it takes for the output frequency to climb from 0% to 100%, while
“deceleration time” refers the time taken for the output frequency drop down to 0%. The default acceleration
time is C1-01, and the default of the deceleration time is C1-02.
Related Parameters
Parameter
Number
Name
Description
Setting
Range
Default
Change
during
Run
Control Methods
Display
V/f
Open
Loop
Vector
Flux
Vector
C1-01
Acceleration Time
1
Sets the time to accelerate from zero to maxi-
mum frequency.
0.0 to
6000.0
*
10.0 s
Yes
Q
Q
Q
Accel Time 1
C1-02
Deceleration Time
1
Sets the time to decelerate from maximum
frequency to zero.
Yes
Q
Q
Q
Decel Time 1
C1-03
Acceleration Time
2
Sets the time to accelerate from zero to maxi-
mum frequency when selected via a multi-
function input.
Yes
A
A
A
Accel Time 2
C1-04
Deceleration Time
2
Sets the time to decelerate from maximum
frequency to zero when selected via a multi-
function input.
Yes
A
A
A
Decel Time 2
C1-05
Acceleration Time
3
Sets the time to accelerate from zero to maxi-
mum frequency when selected via a multi-
function input.
No
A
A
A
Accel Time 3
C1-06
Deceleration Time
3
Sets the time to decelerate from maximum
frequency to zero when selected via a multi-
function input.
No
A
A
A
Decel Time 3
C1-07
Acceleration Time
4
Sets the time to accelerate from zero to maxi-
mum frequency when selected via a multi-
function input.
No
A
A
A
Accel Time 4
C1-08
Deceleration Time
4
Sets the time to decelerate from maximum
frequency to zero when selected via a multi-
function input.
No
A
A
A
Decel Time 4
C1-10
Accel/Decel Time
Setting Units
Sets the setting resolution of C1-01 to C1-09.
0: 0.01 s (0.00 to 600.00 s)
1: 0.1 s (0.0 to 6000.0 s)
0 or 1
1
No
A
A
A
Acc/Dec Units
C1-11
Accel/Decel
Switch Frequency
Sets the frequency for automatic switching of
accel/decel times.
Fout < C1-11: Accel/Decel Time 4
Fout
≥C1-11: Accel/Decel Time 1
Multi-function inputs “Multi-Acc/Dec 1” and
“Multi-Acc/Dec 2” have priority over C1-11.
Note: With Multi-Function Input, Accel/
Decel Time 1 and 2 will take prece-
dence.
0.0 to
120.0
0.0 Hz
No
A
A
A
Acc/Dec SW Freq