E3: motor 2 v/f pattern, E4: motor 2 setup – Yaskawa Matrix Converter User Manual
Page 127
Parameter Tables
5-
27
E3: Motor 2 V/f Pattern
* 1. These are values for a 200 V class MxC. Double the value for a 400 V class MxC.
* 2. The default will change when the control method is changed. The Open Loop Vector defaults are given.
E4: Motor 2 Setup
Parameter
Number
Name
Description
Setting
Range
Default
Change
during
Run
Control
Methods
MEMO-
BUS
Register
Page
Display
V/f
Open
Loop
Vector
Flux
Vector
E3-01
Motor 2 Control
Method Selection
0: V/f Control
2: Open Loop Vector Control
3: Flux Vector Control
0, 2, or
3
2
No
A
A
A
319H
-
Control Method
E3-02
Motor 2 Maxi-
mum Output Fre-
quency
To set V/f characteristics in a straight
line, set the same values for E3-05 and
E3-07. In this case, the setting for E3-06
will be disregarded. Be sure that the four
frequencies are set in the following man-
ner or else an OPE10 fault will occur:
E3-02
≥ E3-04 ≥ E3-05 ≥ E3-07
40.0 to
120.0
60.0
Hz
*2
No
A
A
A
31AH
-
Max Frequency
E3-03
Motor 2 Maxi-
mum Output Volt-
age
0.0 to
255.0
*1
200.0
VAC
*1 *2
No
A
A
A
31BH
-
Max Voltage
E3-04
Motor 2 Base Fre-
quency
0.0 to
120.0
60.0
Hz
*2
No
A
A
A
31CH
-
Base Frequency
E3-05
Motor 2 Mid Out-
put Frequency
0.0 to
120.0
3.0 Hz
*2
No
A
A
No
31DH
-
Mid Frequency
E3-06
Motor 2 Mid Out-
put Voltage VA
0.0 to
255.0
*1
13.0
VAC
*1 *2
No
A
A
No
31EH
-
Mid Voltage
E3-07
Motor 2 Mini-
mum Output Fre-
quency
0.0 to
120.0
0.5 Hz
*2
No
A
A
A
31FH
-
Min Frequency
E3-08
Motor 2 Mini-
mum Output Volt-
age
0.0 to
255.0
*1
2.5
VAC
*1 *2
No
A
A
No
320H
-
Min Voltage
Parameter
Number
Name
Description
Setting
Range
Default
Change
during
Run
Control
Methods
MEMO-
BUS
Register
Page
Display
V/f
Open
Loop
Vector
Flux
Vector
E4-01
Motor 2 Rated
Current
Sets the motor 2 name plate full load cur-
rent in amperes (A). This value is auto-
matically set during Auto-Tuning.
2.70
to
54.00
*2
19.60
A
*1
No
A
A
A
321H
6-51
Motor Rated FLA
E4-02
Motor 2 Rated
Slip
Sets the rated slip of motor 2 in hertz
(Hz). This value is automatically set dur-
ing Rotational Auto-Tuning.
0.00 to
20.00
1.50
Hz
*1
No
A
A
A
322H
-
Motor Rated Slip
E4-03
Motor 2 No-Load
Current
Sets the magnetizing current of motor 2
in percentage of full load current (E4-01).
This value is automatically set during
Rotational Auto-Tuning.
0.00 to
19.59
*3
5.10 A
*1
No
A
A
A
323H
-
No-Load Current
Output voltage (V)
Frequency (Hz)
VMAX
VC
VMIN
FMIN
FB
FA
FMAX