E2: motor setup – Yaskawa Matrix Converter User Manual
Page 126
![background image](https://www.manualsdir.com/files/819680/content/doc126.png)
5
-26
E2: Motor Setup
* 1. The default depends on the MxC capacity. The value for a 200 V class MxC of 5.5 kW is given.
* 2. The setting range is from 10% to 200% of the MxC rated output current. The value for a 200 V class MxC for 5.5 kW is given. The upper limit of the Motor No-
Load Current (E2-03) must be less than the Motor Rated Current (E2-01).
* 3. The setting range depends on the MxC capacity. The value for a 200 V class MxC of 5.5 kW is given.
Parameter
Number
Name
Description
Setting
Range
Default
Change
during
Run
Control
Methods
MEMO-
BUS
Register
Page
Display
V/f
Open
Loop
Vector
Flux
Vector
E2-01
Motor Rated
Current
Sets the motor nameplate full load current
in amperes (A). This value is automati-
cally set during Auto-Tuning.
2.70 to
54.00
*2
19.60
A
*1
No
Q
Q
Q
30EH
4-5
6-51
6-102
Motor Rated FLA
E2-02
Motor Rated Slip
Sets the motor rated slip in hertz (Hz).
This value is automatically set during
Rotational Auto-Tuning.
0.00 to
20.00
1.50
Hz
*1
No
A
A
A
30FH
6-100
6-102
Motor Rated Slip
E2-03
Motor No-Load
Current
Sets the magnetizing current of the motor
as a percentage of full load amps (E2-01).
This value is automatically set during
Rotational Auto-Tuning.
0.00 to
19.59
*3
5.10 A
*1
No
A
A
A
310H
6-102
No-Load Current
E2-04
Number of Motor
Poles
Sets the number of motor poles. This
value is automatically set during Auto-
Tuning.
2 to 48 4 poles
No
No
No
Q
311H
6-102
Number of Poles
E2-05
Motor Line-to-
Line Resistance
Sets the phase-to-phase motor resistance
in ohms. This value is automatically set
by Auto-Tuning.
0.000
to
65.000
0.399
Ω
*1
No
A
A
A
312H
6-102
Term Resistance
E2-06
Motor Leakage
Inductance
Sets the voltage drop due to motor leak-
age inductance as a percentage of motor
rated voltage. This value is automatically
set during Auto-Tuning.
0.0 to
40.0
18.2%
*1
No
No
A
A
313H
6-102
Leak Inductance
E2-07
Motor Iron-core
Saturation Coeffi-
cient 1
Sets the motor iron saturation coefficient
at 50% of magnetic flux. This value is
automatically set during Rotational Auto-
Tuning.
0.00 to
0.50
0.50
No
No
A
A
314H
6-102
Saturation Comp1
E2-08
Motor Iron-core
Saturation Coeffi-
cient 2
Sets the motor iron saturation coefficient
at 75% of magnetic flux. This value is
automatically set during Rotational Auto-
Tuning.
0.50 to
0.75
0.75
No
No
A
A
315H
6-102
Saturation Comp2
E2-09
Motor Mechani-
cal Loss
Sets the motor mechanical loss as a per-
centage of motor rated power (kW)
capacity.
Adjust in the following circumstances:
• When torque loss is large due to motor
bearing friction.
• When the torque loss in the load is
large.
0.0 to
10.0
0.0%
No
No
A
A
316H
-
Mechanical Loss
E2-10
Motor Iron Loss
for Torque Com-
pensation
Sets the motor iron loss in watts (W).
0 to
65535
172 W
*1
No
A
No
No
317H
6-102
Tcomp Iron Loss
E2-11
Motor Rated
Output
Sets the motor rated power in kilowatts
(kW). This value is automatically set dur-
ing Auto-Tuning.
5.50 to
650.00
5.50
kW
*1
No
Q
Q
Q
318H
-
Mtr Rated Power
E2-12
Motor Iron-Core
Saturation Coeffi-
cient 3
Set to the motor iron saturation coeffi-
cient at 130% of magnetic flux.
1.30 to
1.60
1.30
No
No
A
A
328H
6-102
Saturation Comp3