Yaskawa Matrix Converter User Manual
Page 183
6
-18
* The setting range for accel/decel times depends on the setting of C1-10 (Accel/Decel Time Setting Units). If C1-10 is set to 0, the setting range is 0.00 to
600.00 (s).
Setting the Units to Express the Acceleration and Deceleration Time
Set the accel/decel time units using C1-10. The default setting for C1-10 is 1.
Switching Acceleration and Deceleration Time Using Multi-Function Input Terminal
Commands
The MxC allows for four separate acceleration times and four separate deceleration times. When the multi-
function input terminals (H1-) are set to 7 (Accel/Decel Time Selection 1) and 1A (Accel/Decel Time
Selection 2), the accel/decel time of the MxC can be changed even while the application is running based on
the terminal switch status.
The following table shows the possible accel/decel time switching combinations.
C2-01
S-Curve Charac-
teristic at Accel
Start
All sections of the S-curve characteristic time
are set in seconds units.
When the S-curve characteristic time is set,
the accel/decel times will increase by only
half of the S-curve characteristic times at start
and end.
0.00 to
2.50
0.20 s
No
A
A
A
SCrv Acc @ Start
C2-02
S-Curve Charac-
teristic at Accel
End
0.00 to
2.50
0.20 s
No
A
A
A
SCrv Acc @ End
C2-03
S-Curve Charac-
teristic at Decel
Start
0.00 to
2.50
0.20 s
No
A
A
A
SCrv Dec @ Start
C2-04
S-Curve Charac-
teristic at Decel
End
0.00 to
2.50
0.00 s
No
A
A
A
SCrv Dec @ End
Set value
Details
0
The accel/decel time settings range is 0.00 to 600.00 in units of 0.01 s.
1
The accel/decel time settings range is 0.0 to 6000.0 in units of 0.1 s.
Accel/Decel Time
Selection 1 Terminal
Accel/Decel Time
Selection 2 Terminal
Acceleration Time
Deceleration Time
off
off
C1-01
C1-02
on
off
C1-03
C1-04
off
on
C1-05
C1-06
on
on
C1-07
C1-08