Stopping Methods
6-
11
Stopping Methods
This section explains the parameter settings and functions to have the MxC stop the motor.
Selecting the Stopping Method when a Stop Command is Sent
There are four methods of stopping the MxC when a Stop Command is sent:
•
Decelerate to Stop (also referred to as, “Ramp to Stop”)
•
Coast to Stop
•
DC Injection Braking Stop
•
Coast to Stop (with or without a timer)
Set parameter b1-03 to indicate how the MxC should stop the motor. The MxC is unable to coast to stop or use
DC braking when operating in Flux Vector Control.
Related Parameters
Parameter
Number
Name
Description
Setting
Range
Default
Change
during
Run
Control Methods
Display
V/f
Open
Loop
Vector
Flux
Vector
b1-03
Stopping Method
Selection
Selects the stopping method when the Run
Command is removed.
0: Decelerate to stop
1: Coast to Stop
2: DC Injection to Stop
3: Coast with Timer (A new Run Command
is ignored if received before the timer
expires).
0 to 3 *
0
No
Q
Q
Q
Stopping Method
b1-05
Minimum Output
Frequency (E1-09)
or Less Operation
Selection
Operation method when frequency reference
is less than minimum output frequency set in
E1-09.
0: Operates according to frequency reference
(E1-09 is disabled).
1: Output shuts off (coast to stop if less than
E1-09).
2: Operates according to E1-09 (frequency
reference set to E1-09).
3: Zero speed (frequency reference becomes
zero when less than E1-09).
0 to 3
0
No
No
No
A
Zero-Speed Oper
b2-01
DC Injection Brak-
ing Start Fre-
quency
Sets the frequency at which DC injection
braking starts when decelerate to stop (b1-03
= 0) is selected. If b2-01< E1-09, DC Injec-
tion braking starts at E1-09.
Note: Zero Speed restrictions are active in
Flux Vector Mode.
0.0 to
10.0
0.5 Hz
No
A
A
A
DCInj Start Freq
b2-02
DC Injection Brak-
ing Current
Sets the DC injection braking current as a per-
centage of the MxC rated current.
Note: The DC excitation current is deter-
mined by the setting in E2-03 when
operating in Flux Loop Vector Control
Method.
0 to
100
50%
No
A
A
No
DCInj Current
b2-03
DC Injection Brak-
ing Time/DC Exci-
tation Time at Start Sets the time of DC injection braking at start
in units of 0.01 seconds.
0.00
to
10.00
0.00 s
No
A
A
A
DCInj Time
@Start