Yaskawa Matrix Converter User Manual
Page 253
![background image](https://www.manualsdir.com/files/819680/content/doc253.png)
6
-88
Data Tables
The data tables are shown below. The types of data are as follows: Reference data, monitor data, and broadcast
data.
Reference Data
The reference data table is shown below. You can both read and write reference data.
Note: Write 0 to all unused bits. Also, do not write data to reserved registers.
Register No.
Contents
0000H
Not used
0001H
Frequency reference
Bit 0
Forward Run/Stop Command 1: Forward run 0: Stop
Bit 1
Reverse Run/Stop Command 1: Reverse run 0: Stop
Bit 2
External fault
1: Error (EFO)
Bit 3
Fault reset
1: Reset Command
Bit 4
ComNet
Bit 5
ComCtrl
Bit 6
Multi-Function Input Command 3
Bit 7
Multi-Function Input Command 4
Bit 8
Multi-Function Input Command 5
Bit 9
Multi-Function Input Command 6
Bit A
Multi-Function Input Command 7
Bit B
Multi-Function Input Command 8
Bit C
Multi-Function Input Command 9
Bit D
Multi-Function Input Command 10
Bit E
Multi-Function Input Command 11
Bit F
Multi-Function Input Command 12
0002H
Frequency reference (Set units using parameter o1-03)
0003H
Not used
0004H
Not used
0005H
Not used
0006H
PID target value
0007H
Analog output 1 setting (-11 V/-1540 to 10 V/1540)
0008H
Analog output 2 setting (-11 V/-1540 to 11 V/1540)
0009H
Multi-function digital output setting
Bit 0
Contact output (Terminal M1-M2)
1: on
0: off
Bit 1
PHC1 (Contact P1-PC)
1: on
0: off
Bit 2
PHC2 (Contact P2-PC)
1: on
0: off
Bit 3
PHC3 (Contact P3-C3)
1: on
0: off
Bit 4
PHC4 (Contact P4-C4)
1: on
0: off
Bit 5
Not used
Bit 6
Set error contact (terminal MA-MC) output using bit 7. 1: on 0: off
Bit 7
Error contact (terminal MA-MC)
1: on 0: off
Bits 8 to F
Not used
000AH to 000EH Not used
000FH
Reference selection settings
Bit 0
Not used
Bit 1
Use MEMOBUS 0006H PID target value
Bits 2 to B
Not used
C
Broadcast data terminal S5 input 1: Enabled. 0: Disabled.
D
Broadcast data terminal S6 input 1: Enabled. 0: Disabled.
E
Broadcast data terminal S7 input 1: Enabled. 0: Disabled.
F
Broadcast data terminal S8 input 1: Enabled. 0: Disabled.