Yaskawa Matrix Converter User Manual
Page 142
5
-42
H5: MEMOBUS Communications
* Set H5-01 to 0 to disable MxC responses to MEMOBUS communications.
Parameter
Number
Name
Description
Setting
Range
Default
Change
during
Run
Control
Methods
MEMO-
BUS
Register
Page
Display
V/f
Open
Loop
Vector
Flux
Vector
H5-01
MxC Node
Address
Set the MxC's station address.
0 to 20
*
1F
No
A
A
A
425H
6-84
Serial Comm Adr
H5-02
Communication
Speed Selection
Set the baud rate for MEMOBUS com-
munications of communications connec-
tion terminals.
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
0 to 4
3
No
A
A
A
426H
6-84
Serial Baud Rate
H5-03
Communication
Parity Selection
Set the parity for MEMOBUS communi-
cations of CN6.
0: No parity
1: Even parity
2: Odd parity
0 to 2
0
No
A
A
A
427H
6-84
Serial Com Sel
H5-04
Stopping Method
After Communi-
cation Error
Set the stopping method for communica-
tions errors.
0: Deceleration to stop
1: Coast to stop
2: Emergency stop
3: Continue operation
0 to 3
3
No
A
A
A
428H
6-84
Serial Fault Sel
H5-05
Communication
Fault Detection
Selection
Set whether or not a communications tim-
eout is to be detected as a communica-
tions error.
0: Do not detect.
1: Detect
0 or 1
1
No
A
A
A
429H
6-84
Serial Flt Dtct
H5-06
MxC Transmit
Wait Time
Set the time from the MxC receiving data
to when the MxC starts to send.
5 to 65
5 ms
No
A
A
A
42AH
6-84
Transmit Wait-
TIM
H5-07
RTS Control
Selection
Select to enable or disable RTS control.
0: Disabled (RTS is always on)
1: Enabled (RTS turns on only when
sending)
0 or 1
1
No
A
A
A
42BH
6-84
RTS Control Sel
H5-10
Unit Selection for
Memobus Regis-
ter 0025H
Selects the units used for MEMOBUS
registry 0025H (monitors the output volt-
age reference).
0: 0.1 V units
1: 1 V units
0 or 1
0
No
A
A
A
436H
6-84
MEMOBUS 25H
UNIT