Current detection speed search – Yaskawa Matrix Converter User Manual
Page 228

Continuing Operation
6-
63
•
Power Loss Time Longer than the Momentary Power Loss Minimum Baseblock Time (L2-03)
Fig 6.45 Speed Search After Baseblock (Estimated Speed: Loss Time > L2-03)
Current Detection Speed Search
The time charts for current detection speed search are shown below.
Speed Search at Startup
The time chart when speed search at startup or External Speed Search Command is selected is shown below.
Fig 6.46 Speed Search at Startup (Using Current Detection)
Speed Search after Short Baseblock (during Power Loss Recovery, etc.)
•
Loss Time Shorter Than Minimum Baseblock Time
Fig 6.47 Speed Search after Baseblock (Current Detection: Loss Time < L2-03)
AC power supply
Output frequency
Output current
off
on
Start using speed detected
Set frequency
reference
Minimum Baseblock Time
(L2-03)
10 ms
Speed Search Delay Time
(b3-05)
Note: If the frequency immediately before the baseblock is low or the power supply break time is long,
operation may be the same as the search in case 1.
Run Command
Output frequency
Output current
off
on
b3-02
Deceleration time set in b3-03
Set frequency
reference
Minimum Baseblock Time
(L2-03)
Maximum output
frequency or
set frequency
* Lower limit is set using Speed Search Delay Time (b3-05).
*
AC power supply
Output frequency
Output current
off
on
Output frequency before power loss
Set frequency
reference
Minimum Baseblock Time (L2-03)
*1 Baseblock time may be reduced by the output frequency
immediately before baseblock.
*2 After AC power supply recovery, motor waits for the minimum
Speed Search Delay Time (b3-05).
Deceleration
time set in b3-03
b3-02
Speed Search Deactivation Current
*2
*1