Parameter Tables
5-
37
H2: Multi-Function Contact Outputs
Multi-Function Contact Output Functions
Parameter
Number
Name
Description
Setting
Range
Default
Change
during
Run
Control
Methods
MEMO-
BUS
Register
Page
Display
V/f
Open
Loop
Vector
Flux
Vector
H2-01
Terminal M1 thru
M2 Function
Selection (Relay)
Multi-function contact output
0 to 37
0
No
A
A
A
40BH
-
Term M1-M2 Sel
H2-02
Terminal M3-M4
Function Selec-
tion (Relay)
Multi-function contact output 1
0 to 37
1
No
A
A
A
40CH
-
Term P1 Sel
H2-03
Terminal M5-M6
Function Selec-
tion (Relay)
Multi-function contact output 2
0 to 37
2
No
A
A
A
40DH
-
Term P2 Sel
H2-04
Terminal P3
Function Selec-
tion (Open Col-
lector)
Multi-function contact output 3
0 to 37
6
No
A
A
A
40EH
-
Term P3 Sel
H2-05
Terminal P4
Function Selec-
tion (Open Col-
lector)
Multi-function contact output 4
0 to 37
10
No
A
A
A
40FH
-
Term P4 Sel
Set
Value
Function
Control
Methods
Page
V/f
Open
Loop
Vector
Flux
Vector
0
During Run (ON: Run Command is on or voltage is being output)
Yes
Yes
Yes
6-77
1
Zero-speed
Yes
Yes
Yes
6-77
2
Frequency agree 1 (L4-02 used).
Yes
Yes
Yes
6-45
3
Desired frequency agree 1 (ON: Output frequency = ±L4-01, L4-02 used and during
frequency agree)
Yes
Yes
Yes
6-45
4
Frequency (FOUT) detection 1 (ON: +L4-01
≥ output frequency ≥ -L4-01, L4-02
used)
Yes
Yes
Yes
6-45
5
Frequency (FOUT) detection 2 (ON: Output frequency
≥ +L4-01 or output frequency
≤ -L4-01, L4-02 used)
Yes
Yes
Yes
6-45
6
MxC operation ready
READY: After initialization, no faults
Yes
Yes
Yes
-
7
During detection of power voltage fault (FDV, AUV, or UV)
Yes
Yes
Yes
-
8
During baseblock (ON: during baseblock)
Yes
Yes
Yes
-
9
Frequency reference selection (ON: Frequency reference from Operator)
Yes
Yes
Yes
-
A
Run Command selection status (ON: Run Command from Operator)
Yes
Yes
Yes
-
B
Overtorque/undertorque detection 1 NO (NO contact: Overtorque/undertorque detec-
tion at on)
Yes
Yes
Yes
6-49
C
Loss of frequency reference (Enabled when 1 is set for L4-05)
Yes
Yes
Yes
6-64