Connecting analogue matrix switches (Bridging)

188 · G&D DVICenter

Requirements

You can use a console connected to the digital matrix switch to access a target module

connected to the analogue matrix switch if the following requirements are met:

1. The matrix switches and the modules of the Bridge line are placed in the correct

order (see figure 1) and are properly connected.

2. The

VGA-CPU

target module is connected to a port operated in Down mode

(see Port administration on page 17).

3. Both matrix switches are connected to the same TCP/IP network.

4. Set the system time of both matrix switches correctly, or use an NTP server for

automatic time adjustment (see page 35 f.).

5. The premium function

IP-Control-API

is enabled for the analogue matrix switch

CATCenter NEO

.

6. The Bridge mode of the target module

VGA-CPU

is configured (see page 188).

Particularities

Bridge lines can be connected only to the digital Master matrix switch of the KVM

system.

Target modules (

CATpro2

) of an analogue matrix switch cannot be used for the

Tradeswitch function (see page 159 ff.).

Configuration

The Bridge mode of a

VGA-CPU

target module is enabled by entering the device ID of

the connected

UCON

user module and the IP address of the analogue matrix switch

CATCenter NEO

.

Enabling the Bridge mode of a target module

How to enable the Bridge mode of a target module:

1. In the directory tree, click

KVM matrix system > [Name] > Target modules

.

2. Right-click the Bridge module (

VGA-CPU

) you want to configure and click

Configu-

ration

on the context menu.

IMPORTANT:

When used in Bridge mode, the user module

UCON

automatically

switches to Open Access mode (see Open Access operating mode on page 100).
At this user module, access is not protected through authentication!

NOTE:

After the Bridge mode of a target module is enabled, the module is listed

in the directory tree under

KVM matrix system > [Name] > Bridge modules

.

NOTE:

Bridge modules are not listed in the OSD of the matrix switch.